Configure the Module for a SmartGuard Controller
Chapter
7
5.
From the Connection Type pull-down menu, for this example choose
Multicast.
6.
From the Configuration pull-down menu, for this example choose
Configuration signature must match.
7.
In the Requested Packet Interval (RPI) box, enter 10 ms.
8.
In the Connection Reaction Time Limit (CRTL), enter 40.1 ms.
9.
Click Add.
This limits the packet size for normal communication. If detailed status is
required when a fault occurs, that data can be read explicitly via MSG
instructions.
10.
Repeat steps
3…9
for each connection, being sure to assign input and
output connections.
Notice that the connections for the 1734-IB8S module have 2 bytes. If you
had selected individual point status, the input connection would be
5 bytes.
11.
Click Apply.
For further details, see the SmartGuard 600 Controllers User Manual,
publication
1752-UM001
, and SmartGuard 600 Controllers Safety
1752-RM001
.
Содержание 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S Installation User Manual...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013C EN P August 2010 Summary of Changes Notes...
Страница 38: ...38 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 2 Safety Functions Notes...
Страница 52: ...52 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 3 Install the Module Notes...
Страница 58: ...58 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 4 Wire the Module Notes...
Страница 64: ...64 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 5 Power Supply Examples Notes...
Страница 144: ...144 Rockwell Automation Publication 1734 UM013C EN P August 2010 Appendix D Specifications Notes...
Страница 153: ......
Страница 154: ......
Страница 155: ......