Wiring Examples
Chapter 4
Emergency stop switch
Door monitor
Yes
Connect the switches
between I0 and T0, and
I1 and T1
4
E
Emergency stop switch
Door monitor
No
Connect the switches
between T0 and I0 and
I1. T0 is configured for
24V power supply.
3
D
Connect the switches
between 24V DC and I0
and I1.
D
Table 21 - Input Device Connection Methods and Safety Categories (Continued)
Connected Device
Test Pulse
from Test
Output
Connection
Schematic Diagram
Safety
Category
Maximum
Performance
Level
1
4
5
2
3
I0
I1
T0
T1
1791ES Modules
1732ES Modules
1 - Test Output 1
2 - Input 1
3 - Input Common
4 - Input 0
5 - Test Output 0
I0
I1
T0
T1
1
4
5
2
3
1791ES Modules
1732ES Modules
1 - Test Output 1
2 - Input 1
3 - Input Common
4 - Input 0
5 - Test Output 0
I0
I1
T0
T1
24V DC
1
4
5
2
3
1791ES Modules
1732ES Modules
24V DC
1 - Test Output 1
2 - Input 1
3 - Input Common
4 - Input 0
5 - Test Output 0
Содержание 1732ES-IB12XOB4
Страница 6: ...6 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Summary of Changes Notes ...
Страница 38: ...38 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Chapter 2 About the Modules Notes ...
Страница 174: ...174 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Index Notes ...
Страница 175: ......