26
Rockwell Automation Publication 1606-RM008A-EN-P - November 2021
DC-UPS - 24V, 20 A, 480 W Reference Manual
Dielectric Strength
The signal port (relay contacts and inhibit input) are floating and separated
from the power port (input voltage, output voltage, center-tap terminal and
temperature sensor).
Type and factory tests are conducted by the manufacturer. Field tests may be
conducted in the field using the appropriate test equipment that applies the
voltage with a slow ramp (2 s up and 2 s down). Connect all poles of the power
port terminals together and all poles of the signal port before conducting the
test. When testing, set the cutoff current settings to the value in the following
table. The following isolation tests were performed:
Figure 19 - Dielectric Strength
Certifications and
Standards Compliance
A
B
C
Type test
60 s
1060V AC
1060V AC
1060V AC
Factory Test
5 s
650V AC
650V AC
650V AC
Field Test
5 s
500V AC
500V AC
500V AC
Cutoff current setting
> 90 mA
> 1 mA
> 1 mA
Input, Output,
Battery,
Temperature
Sensor,
Center-tap
Chassis
Signal Port
A
C
B
UL 508
UL Certificate Listed equipment for category NMTR - Industrial Control Equipment Applicable for US and Canada
UL 60950-1
UL Certificate Recognized component for category QQGQ - Information Technology Equipment (ITE) Applicable for US and
Canada
ATEX (1606-
XLS480-UPS)
Agency Certificate (Bureau Veritas) EN 60079-0 Explosive atmospheres - General requirements EN 60079-7, EN 60079-15
Equipment protection by type of protection “e” and “n” Certificate: EPS 15 ATEX 1 025 X Temperature Code: T4 Type of
Protection: EC nC
IECEx (1606-
XLS480-UPS)
IECEx Certificate IEC 60079-0 Explosive atmospheres - General requirements IEC 60079-7, IEC 60079-15 Equipment
protection by type of protection “e” and “n” Certificate: IECEx EPS 15.0049X Temperature Code: T4 Type of Protection: EC
nC
Class I Div 2 (1606-
XLS480-UPS)
CSA Certificate Power Supplies for Hazardous Location Applicable for Canada and US CSA Class: 5318-01 (Canada), 5318-81
(USA) Temperature Code: T4 Groups: A, B, C, and D
Marine (DNV)
DNV Certificate DNV Type approved product Certificate: TAA00002JT Temperature: Class D Humidity: Class B Vibration:
Class C EMC: Class A Enclosure: Class A
Содержание 1606-XLS480-UPS
Страница 1: ...Reference Manual Original Instructions DC UPS 24V 20 A 480 W Catalog Number 1606 XLS480 UPS ...
Страница 4: ...4 Rockwell Automation Publication 1606 RM008A EN P November 2021 Table of Contents Notes ...