Rockwell Automation Publication 1606-RM110A-EN-P - July 2020
21
Redundancy Power Supply - 24V, 10 A, 240 W, Single-phase Input
Safety and Protection
Features
Isolation resistance
Min
500 MΩ
At delivered condition between input and output, measured with 500V DC
Min
500 MΩ
At delivered condition between input and PE, measured with 500V DC
Min
500 MΩ
At delivered condition between output and PE, measured with 500V DC
Min
500 MΩ
At delivered condition between output and DC OK contacts, measured with 500V DC
PE resistance
Max
0.1O Ω
Resistance between PE terminal and the housing in the area of the DIN rail mounting bracket.
Output overvoltage protection
(1)
Typ
30.5V DC
In case of an internal defect, a redundant circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Max
32V DC
Class of protection
I
According to IEC 61140
A PE (Protective Earth) connection is required
Degree of protection
IP 20
According to EN/IEC 60529
Over-temperature protection
(2)
Included
Output shut-down with automatic restart. Temperature sensors are installed on critical
components inside the unit and turn the unit off in safety critical situations, which can happen e.g.
when ambient temperature is too high, ventilation is obstructed or the derating requirements are
not followed. There is no correlation between the operating temperature and turn-off temperature
since this is dependent on input voltage, load and installation methods.
Input transient protection
MOV (Metal Oxide Varistor) For protection values see
EMC on page 19
Internal input fuse
Included
Not user replaceable slow-blow high-braking capacity fuse
Touch current (leakage current)
Typ
0.14 mA / 0.36 mA
At 100V AC, 50Hz, TN-,TT-mains / IT-mains
Typ
0.20 mA / 0.50 mA
At 120V AC, 60Hz, TN-,TT-mains / IT-mains
Typ
0.33 mA / 0.86 mA
At 230V AC, 50Hz, TN-,TT-mains / IT-mains
Max
0.18 mA / 0.43 mA
At 110V AC, 50Hz, TN-,TT-mains / IT-mains
Max
0.26 mA / 0.61 mA
At 132V AC, 60Hz, TN-,TT-mains / IT-mains
Max
0.44 mA / 1.05 mA
At 264V AC, 50Hz, TN-,TT-mains / IT-mains
(1)
In case of an internal defect, a redundant circuit limits the maximum output voltage. The output shuts down and automatically attempts to restart.
(2) Temperature sensors are installed on critical components inside the unit and turn the unit off in safety critical situations, which can happen for example, when ambient temperature is too
high, ventilation is obstructed or the derating requirements are not followed. There is no correlation between the operating temperature and turn-off temperature since this is dependent
on input voltage, load and installation methods.