Rockwell Automation Publication 1606-RM111A-EN-P - July 2020
13
Physical Dimensions and
Weight
Attributes
Values and Descriptions
Width
39 mm (1.54 in.)
Height
124 mm (4.88 in.)
Depth
124 mm (4.88 in.)
The DIN rail height must be added to the unit depth to calculate the total required installation depth.
Weight
280 g (0.62 lb)
DIN rail
Use 35 mm (1.38 in.) DIN rails according to EN 60715 or EN 50022 with a height of 7.5 mm (0.295 in.) or 15 mm (0.59 in.).
Plastic Material of Housing
Flame retardant Polycarbonate (PC) - UL94-V0
Vicat softening temperature specified with 149 °C (300 °F) according to ASTM D1525
Installation Clearances
Keep the following installation clearances:
• 40 mm (1.57 in.) on the top
• 20 mm (0.79 in.) on the bottom
• 5 mm (0.20 in.) on the left and right sides are recommended when the device is loaded permanently with more than
50% of the rated output current. Increase the side clearances to 15 mm (0.59 in.) if the adjacent device is a heat
source, such as a power supply.
Figure 10 - Front View
Figure 11 - Side View