background image

Digital I/O Conversion Module

(Cat 1492-CM1771-LD005)

PN-114277

DIR 10000060088 

(Version 01)

Publication 1492-IN035B-EN-E

Printed in U.S.A.

I. Description

This Digital I/O Conversion Module provides for the conversion of (1) 1771, 32 point I/O modules to be converted to 
(1) 1756, 32 point I/O module and consists of the following:

(1) 1771 Module (32pt) to (1) 1756 Module (32pt)

(2) Conversion Module:  1492-CM1771-LD005 
(1) Cable:  1492-CONCAB005Z (Table 2, Section III)
(1) Conversion Mounting Assembly:  1492-MUA… (Table 1, Section II)

This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm.  The exist-
ing 1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module.  On one end of the 1492 
Cable is (1) connector for the Conversion Module.  On the other end is the Removable Terminal Block (RTB) for the 
1756 I/O module, as shown in the photo below.  The I/O signals are routed through the 1492 Conversion Module and 
the 1492 Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in Section V.  As stan-
dard, both portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length.  Refer to the footnotes in 
Table 2, Section III for further details.

De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis, 
and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any 
device in the control cabinet where the conversion is to be performed.  Ensure work is performed by 
qualified personnel.

WARNING

1492-CM1771-LD005 Conversion Module

Conversion Compatibility and
Product I.D. Label

37-Pin Connector for cable 1492-CONCAB

Z

Содержание 1492-CM1771-LD005

Страница 1: ...s 1 connector for the Conversion Module On the other end is the Removable Terminal Block RTB for the 1756 I O module as shown in the photo below The I O signals are routed through the 1492 Conversion Module and the 1492 Cable to the appropriate terminals on the 1756 I O module per the Wiring Diagrams in Section V As stan dard both portions of the 1492 Cables are 0 5M long but we also offer a 1 0M ...

Страница 2: ...e The combined Depth of the 1492 Conversion Mounting Assembly with the 1756 Chassis mounted on top is 10 25 inches Controller w key or 10 0 inches Controller w o key Dimension drawings are included in the System Installation Manual that ships with the 1492 Conversion Mounting Assembly Foot Notes 1771 A3B is not listed as it is used for 19 inch wide instrumentation panels Notice that the 1756 Chass...

Страница 3: ...92 Conversion Module 1492 Cable 1771 IVN 1756 IV32 1492 CM1771 LD005 1492 CONCAB005Z Specification Dimensions Approximate Shipping Weight 11 81 in height x 4 38 in depth x 1 5 in width 300 mm height x 111 25 mm depth x 38 1 mm width 242 1 g 0 53 lbs includes carton Storage Temperature 40 to 85 C 40 to 185 F Operating Temperature 0 to 60 C 32 to 140 F Operating Humidity 5 to 95 at 60 C non condensi...

Страница 4: ... Black White Orange White Red Orange Orange White Blue IN 15 16 IN 31 34 17 DC 0 White Red Blue DC 1 35 Input 01 Input 01 Input 02 Input 02 Input 03 Input 03 Input 04 Input 04 Input 05 Input 05 Input 06 Input 06 Input 07 Input 07 Input 10 Input 11 Input 10 Input 12 Input 13 Input 13 Input 14 Input 14 Input 15 Input 15 Input 16 Input 16 Input 17 Input 17 Input 00 19 39 20 40 1 11 23 10 30V dc 0 3 I...