Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
541
CIP Objects
Appendix A
Common Codes and
Structures
Table 314 - Generic CIP Status Codes
Code
Name
Description
0x00 (0)
Success
Service was successfully performed by the object specified.
0x01 (1)
Connection failure
A connection-related service failed along the connection path.
0x02 (2)
Resource unavailable
Resources are needed for the object to perform the requested service were unavailable.
0x03 (3)
Invalid parameter value
See Status Code 0x20, which is the preferred value to use for this condition.
0x04 (4)
Path segment error
The path segment identifier or the segment syntax was not understood by the processing node. Path
processing stops when a path segment error is encountered.
0x05 (5)
Path destination unknown
The path is referencing an object class, instance, or structure element that is not known or is not
contained in the processing node. Path processing stops when a path destination unknown error is
encountered.
0x06 (6)
Partial transfer
Only part of the expected data was transferred.
0x07 (7)
Connection lost
The messaging connection was lost.
0x08 (8)
Service not supported
The requested service was not implemented or was not defined for this Object Class/Instance.
0x09 (9)
Invalid attribute value
Invalid attribute data detected.
0x0A (10)
Attribute list error
An attribute in the Get Attribute List or Set Attribute List response has a nonzero status.
0x0B (11)
Already in requested
mode/state
The object is already in the mode/state requested by the service.
0x0C (12)
Object state conflict
The object cannot perform the requested service in its current mode/state
0x0D (13)
Object already exists
The requested instance of object to be created already exists.
0x0E (14)
Attribute not settable
A request to modify a non-modifiable attribute was received.
0x0F (15)
Privilege violation
A permission/privilege check failed.
0x10 (16)
Device state conflict
The current mode/state of the device prohibits the execution of the requested service.
0x11 (17)
Reply data too large
The data to be transmitted in the response buffer is larger than the allocated response buffer.
0x12 (18)
Fragmentation of a primitive
value
The service specified an operation that is going to fragment a primitive data value, such as half a
REAL data type.
0x13 (19)
Not enough data
The service did not supply enough data to perform the specified operation.
0x14 (20)
Attribute not supported
The attribute that is specified in the request is not supported.
0x15 (21)
Too much data
The service supplied more data than was expected.
0x16 (22)
Object does not exist
The object that is specified does not exist in the device.
0x17 (23)
Service fragmentation sequence not in progress
The fragmentation sequence for this service is not currently active for this data.
0x18 (24)
No stored attribute data
The attribute data of this object was not saved before the requested service.
0x19 (25)
Store operation failure
The attribute data of this object was not saved due to a failure during the attempt.
0x1A (26)
Routing failure, request packet too large
The service request packet was too large for transmission on a network in the path to the
destination. The routing device was forced to abort the service.
0x1B (27)
Routing failure, response packet too large
The service response packet was too large for transmission on a network in the path from the
destination. The routing device was forced to abort the service.
0x1C (28)
Missing attribute list entry data
The service did not supply an attribute in a list of attributes that the service needed to perform the
requested behavior.
0x1D (29)
Invalid attribute value list
The service is returning the list of attributes that are supplied with status information for those
attributes that were invalid.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...