Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
455
CIP Objects
Appendix A
Dynamix Voted Alarm Object
This voted/complex alarm object (class object 0x397) defines the
configuration of multiple input voted measurement alarms, the resulting alarm
behavior, and provides access to the associated logical alarm status.
Class attributes and services allow for alarm history information.
Unused instances exist and are accessible but have a disabled state.
Table 185 - Object Instances
Instance ID
Description
0
Voted Alarm Class Instance
1…13
Voted Alarm object instances 1…13
Table 186 - Class Attributes
Attribute
ID
Access
Rule
NV
Name
Data
Type
Description of Attribute
Semantics of
Values
1
Get
NV
Revision
UINT
Current object revision.
Current revision.
8
Get
V
Instances
WORD
Defines the enabled voted
alarm instances.
Bit coding (13 used)
9
Get
V
Common Alert
BOOL
Boolean status indicates the
presence of at least one alert
condition.
10
Get
V
Common
Danger
BOOL
Boolean status indicating
presence of at least one
danger condition.
11
Get
V
Common TX
Fail
BOOL
Boolean status indicates the
presence of at least one TX
Fail condition.
12
Get
V
First Out Alarm
STRUCT
Record of first logical alarm
event (Time Stamp,
measurement output, alarm
status) logged after reset of
First Out alarm option.
13
Get
V
Alarm History
STRUCT
Array of events (Time Stamp,
measurement output, alarm
status) that represents last x
number of entries. A change
in the alarm status triggers
an entry.
16
Get
V
Trip Inhibit/
Bypass Source
BYTE
Source definition for Trip
Inhibit/Bypass
Source selection
17
Get
V
Alarm Reset
Source
BYTE
Source definition for Reset
function
Source selection
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...