Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
415
CIP Objects
Appendix A
Dynamix Transducer Object
The transducer object (class code 0x38E)defines the properties of the sensor
that is connected to one of the four available physical inputs.
Attributes describe physical measurement parameters and transducer OK
monitoring setup, as also some sensor-mounting geometry settings.
This object reports transducer DC Volts (bias) measurement and transducer
status.
Table 144 - Object Instances
Instance ID
Description
0
Transducer Class Instance
Table 145 - Class Attributes
Attribute
ID
Access
Rule
NV
Name
Data
Type
Description of
Attribute
Semantics of Values
1
Get
NV
Revision
UINT
Current object revision.
Current revision.
8
Get
V
TX Overall Status
BYTE
Coded information to
represent transducer
Enabled and OK status
Bits 0…3 represent
transducer
enabled status (1 =
enabled).
Bits 4…7 represent
transducer OK status (1
= OK).
Table 146 - Instance Attributes
Attribute ID
Access Rule
NV
Name
Data Type
Description of Attribute
Semantics of Values
1
Get
V
DC Bias
REAL
The DC level at the input in fixed
units of DC Volts.
Data
2
Get
V
TX Detailed Status
BYTE
Detailed bit-coded Transducer
Status (Data).
See TX OK Configuration Decoding
Transducer Descriptions
Group of four attributes that are used for reference purposes only.
16
Get
V
Transducer Name
SINT[32]
Descriptive name.
32 characters
17
Get
V
Transducer Orientation
INT
Definition of sensor orientation
angle in degrees. Orientation
angle is usually a radial angular
orientation.
0…359 degree input range in
increments of 1 °
18
Get
V
Transducer Location
SINT
Transducer location definition.
0: Unknown
1: Radial
2: Axial
19
Get
V
Transducer Output Sense
SINT
Sensor output sense - information
only. The DC measurement object
has normal/counter control.
Fixed at zero
Transducer Output Definition
Group of five configuration attributes.
24
Get
V
Transducer AC Units
ENGUNITS
Transducer measurement units
that are used for AC measurement
base.
Supported engineering units
25
Get
V
Transducer AC Sensitivity
REAL
TX AC Sensitivity in mV/TX AC
units.
Range: 1…20000
26
Get
V
Transducer DC Units
ENGUNITS
Transducer measurement units
that are used for DC measurement
base.
Supported engineering units
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......