Operate the Module
Chapter 10
Output Assembly
The output assembly consists of one control integer optionally followed by two
speed values and/or an array of 16 alarm values. The speed and/or alarm limit
values are present when specified in Module Definitions.
The control integer is an array of bits, and each bit manages a specific control
function as defined in this table.
Table 71 - Output Assembly
Control
Description
TripInhibit
Trip Inhibit (Bypass)
When set, Trip Inhibit (Bypass) helps prevent any alarm activation (and/or cancel standing alarms), including the
associated alarm action (relay). When Inhibit is set, all relays are held in their non-alarm state.
SetPointMultiplier0En
Set Point Multiplier 0 Enable
When toggled, the module starts (restart) the Hold timer of any voted alarm with the respective Set Point Multiplier
(SPM) control enabled. While the timer is >0, the set points of any associated measurement alarms are multiplied by
the configured factor for the alarm.
SetPointMultiplier1En
Set Point Multiplier 1 Enable
Speed0Fault
Speed 0 Fault
When speed is passed on the output (two speed values following this) these controls allow definition of the status of
the speed values. If set (1) the speed transducer status is considered in fault.
Speed1Fault
Speed 1 Fault
AlarmControl0
Alarm Control 0 Active
If the respective Alarm Control for
Output Tag Gate Control
is specified, then when set, the gate condition is satisfied
and (unless other gate conditions are also specified) the alarm is applied.
If the respective Alarm Control for
Output Tag Override Control
is specified, then when set, the voted alarm
actuates, irrespective of other configurations for the voted alarm.
AlarmControl1
Alarm Control 1 Active
AlarmReset
Alarm Reset
Resets all latched alarms where the alarm condition is no longer present.
AlarmBufferTrigger
Trend Alarm Buffer Trigger
When set, the Alarm Buffer captures the current Trend Buffer and high-resolution data buffer.
AlarmBufferReset
Trend Alarm Buffer Reset
Resets the alarm buffer, if latched. When reset, existing alarm buffer content is lost.
TransientBuffer0Reset
Transient Buffer 0 Reset
Resets the transient buffer, if latched. When reset, existing transient buffer content is lost.
TransientBuffer1Reset
Transient Buffer 1 Reset
TransientBuffer2Reset
Transient Buffer 2 Reset
TransientBuffer3Reset
Transient Buffer 3 Reset
MaxSpeedReset
Maximum Speed Reset
Resets the maximum speed value. When reset, the maximum speed value is set equal to the current measured speed.
Optional Outputs
Speed[2]
Speed Outputs
Optional speed outputs. Provides speed (RPM) to module from the controller.
AlarmLimits[16]
Alarm Limits Output
Optional alarm limit outputs. Provides alarm limits to module from the controller.
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......