Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
285
Operate the Module
Chapter 10
Table 67 - Alarm Status
The alarm number is presented in the assembly in bit format. The alarm
instance is the decimal value that is represented by the 4 bits. For example:
Tag Description
Activated
Activated One or more associated relay outputs (and status indicators) are set
Disabled
Disabled Alarm is disabled
Latching
Latching Configured as latching
Alarming
Alarming Required conditions for the “alarm state” are true
Bypassed
Bypassed Alarm is bypassed (associated relays / status indicators that are held in non-alarm state
SetPointMultActive
Set Point Multiplier is active
FirstOut
First Out Set if the first alarm to activate since last Reset or Bypass
VotedAlarmInstance0
4 bit value.
The number of the Voted Alarm that the status refers to.
Value is 1…13, which references voted alarm 0…12 (so, is Voted Alarm 1).
VotedAlarmInstance1
VotedAlarmInstance2
VotedAlarmInstance3
VotedAlarmStatus0
2 bit value.
Voted Activate Status to Activate On: 0=Normal, 1=Alert, 2=Danger, 3=TX Fault
VotedAlarmStatus1
Inp0MeasAlarmState
Input Measurement Alarm 0 State of the measurement alarm that is referenced for alarm input 0(1)
Inp0MeasAlarmXdcrOK
Input Measurement Alarm 0 TX OK TX OK status of the measurement alarm that is referenced for alarm input 0
Inp1MeasAlarmState
Input Measurement Alarm 1 State of the measurement alarm that is referenced for alarm input 1(1)
Inp1MeasAlarmXdcrOK
Input Measurement Alarm 1 TX OK TX OK status of the measurement alarm that is referenced for alarm input 1
Inp2MeasAlarmState
Input Measurement Alarm 2 State of the measurement alarm that is referenced for alarm input 2(1)
Inp2MeasAlarmXdcrOK
Input Measurement Alarm 2 TX OK TX OK status of the measurement alarm that is referenced for alarm input 2
Inp3MeasAlarmState
Input Measurement Alarm 3 State of the measurement alarm that is referenced for alarm input 3(1)
Inp3MeasAlarmXdcrOK
Input Measurement Alarm 3 TX OK TX OK status of the measurement alarm that is referenced for alarm input 3
SpeedGateActive
Speed Gate Status 0 = not gating, 1 = gating
SpeedGateXdcrOK
Speed Gate TX OK TX OK status of the input that is used for speed gating
LogixGate0Active
Indicates that the first of the up to three gate controls is set.
Gate control can be defined using the output tags AlarmControl0/1 and the Discrete Inputs Pt0 and Pt1.
LogixGate1Active
Indicates that the second of the up to three gate controls is set.
When multiple gate controls are defined, the gate is TRUE when all controls are set
LogixGate2Active
Indicates that the third of the up to three gate controls is set.
When multiple gate controls are defined, the gate is TRUE when all controls are set
LogixControlActive
Indicates that Logic Control is set.
Alarm Logic can be controlled (forced true) using output tags AlarmControl0/1 or either Discrete Input Pt0 or Pt1.
ModuleFaultOrBypass
Indicates that the relay is being bypassed, if configured to trip on bypass, or that the module is in fault, if the relay is
configured to trip on module fault.
-test:I.AlarmStatus[0].VotedAlarmInstance0
0
-test:I.AlarmStatus[0].VotedAlarmInstance1
1
-test:I.AlarmStatus[0].VotedAlarmInstance2
0
-test:I.AlarmStatus[0].VotedAlarmInstance3
0
Содержание 1444-AOFX00-04RB
Страница 10: ...10 Rockwell Automation Publication 1444 UM001D EN P June 2018 Table of Contents Notes...
Страница 12: ...12 Rockwell Automation Publication 1444 UM001D EN P June 2018 Preface Notes...
Страница 198: ...198 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 5 Configure the Tachometer Expansion Module Notes...
Страница 210: ...210 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 7 Configure Relays Notes...
Страница 230: ...230 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 8 Configure Alarms Notes...
Страница 240: ...240 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 9 Trend and Transient Capture Notes...
Страница 316: ...316 Rockwell Automation Publication 1444 UM001D EN P June 2018 Chapter 10 Operate the Module Notes...
Страница 549: ......