218
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix D
Specifications
Environment
Agency Certifications
Schedule of Limitations
Mount this equipment in an IEC 60079-15 certified enclosure with a minimum
ingress protection rating of at least IP54 (as defined in IEC 60529) and used in
an environment of not more than Pollution Degree 2 (as defined in IEC
60664-1) when applied in Zone 2 environments. Provide transient protection
limiting transient to 140% of rated voltage. Do not connect or disconnect
components unless power is switched off.
Attribute
Value
Temperature, operating
-20…70 °C (-4…158 °F)
Temperature, storage
-40…85 °C (-40…185 °F)
Humidity, operating
5…95% (noncondensing)
Shock, operating
30 g
Shock, nonoperating
50 g in 3 perpendicular planes
Vibration, operating
10…500 Hz, 5.0 g / 0.015 in. Max (p-p)
2 hours each axis
Dielectric strength
Tested per IEEE 421.3
Salt fog
Tested per MIL-STD-810E, Method 509.3
Region
(1)
,
(2)
Certification / Compliance
Standard
USA and Canada
Class I, Zone 2,
AEx [ic] nA IIC T4, Ex [ic] nA IIC T4 Gc
UL60079-0 6th Edition / CSA60079-0:11
UL60079-11 6th Edition / CSA60079-11:11
UL60079-15 4th Edition / CSA60079-15:12
Class I, Division 2, Groups A, B, C, or D
UL File E220640
ANSI/ISA 12.12.01-2013 / CSA C22.2 No. 213-M1987
Europe
II 3G Ex [ic] nA IIC Gc (DEMKO 14 ATEX 1230U)
IECEx UL 14.0018U
EN 60079-0:2012 + A11:2013
EN 60079-11:2012
EN 60079-15:2010
EN ISO/IEC-80079-34:2011
CE Compliance
EN 60947-1: Low voltage switch and control gear requirements
EN 50081-2: Electromagnetic compatibility emissions
EN 61000-4-2: Electromagnetic compatibility immunity
EN 61000-4-2: ESD Immunity
ENV 50204: Radiated immunity (Pulse)
EN 61000-4-3: Radiated immunity (Continuous)
EN 61000-4-4: Fast transient immunity
EN 61000-4-5: Surge immunity
EN 61000-4-6: Conducted immunity
EN 61000-4-8: Power frequency magnetic field
EN 55011: Conducted emissions/ Radiated emissions
EN 61000-4-11: Line related tests
(1) A 24V Nominal Battery or 24V DC Power Supply with ATEX certification powers the unit.
(2) Use wire that is rated to 105 °C (221 °F) minimum.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......