CGCM-DLR Unit Configuration
Chapter
4
•
Validate and graph button – Updates the graph that is shown on the
Current tab to display the selected over-current characteristic curve. The
specific curve that is selected by the over-current time dial setting is
displayed in black.
Related Parameters
•
GenRated_I
•
GenRated_V
Frequency Page
The Frequency page is used to configure the parameters that are related to the
over-frequency and under-frequency protection functions.
•
Over-frequency setpoint - Establishes the generator over-frequency
setpoint. The tag
OvrFreqSetpt
in the configuration table stores this
parameter, expressed in Hz.
•
Over-frequency Delay - Establishes the amount of time in seconds that the
frequency must be above the over-frequency setpoint before the
CGCM-DLR unit annunciates the fault. This parameter is stored in tag
OvrFreqTimeDly
in the configuration table.
•
Under-frequency setpoint - Establishes the generator under-frequency
setpoint. The tag
UndrFreqSetpt
in the configuration table stores this
parameter, expressed in Hz.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......