Voltage:
three RMS voltage results that express line-to-line (delta
wiring modes) or line-to-neutral (all other wiring modes) for the
current
Cycle number.
Range 0.0 to 999.0 * 10
21
•
Current:
four RMS current results (L1, L2, L3, L4) for the current
Cycle number.
Range 0.0 to 999.0 * 10
21
•
Trigger channel:
indicates which channel caused the transient
capture. 1=V1, 2=I1, 3=V2, 4=I2, 5=V3, 6=I3, 7=I4
•
Index at trigger:
the value of the transient index at the time of
the capture. Range -999.0 * 10
3
to 999.0 * 10
3
•
Voltage and Current trigger thresholds:
at the time of the
transient capture. Range 0.0 to 999.0 * 10
3
•
Capture ID:
unique identifier that increments by 1s to 30,000 and
then rolls over to 0
Read this data table using an indexed read method. Select the
Read-back Mode, Capture
and
Cycle
by writing to Table A.43.
Reading Transient Capture Data
The data client sets up the read-back configuration with a table write
to Table A.45 Transient Capture Clear/Read-Back Data Select.
Transient capture data is not available via Modbus communications.
This read/write table of 13 integer elements contains the following
•
Password:
required for
Clear
command, use -1 for read-back
selections
•
DeviceNet unique write identifier
•
Capture number:
selects one of 6 captures or returns the last
capture number selected. Range: 0 = most recent capture
initiated via communications, 1 through 6 = capture #1 through
#6, default 1.
•
Channel number:
selects a channel number or returns the last
channel number selected. Range: 1 = V1, 2 = I1, 3 = V2, 4 = I2, 5
= V3, 6 = I3, 7 = I4, default 1.
•
Block number:
selects a data block for the next read or returns
the last block selected. Range depends on communications type.
See below. Default 1.
•
Read-back mode:
selects a read-back mode or returns the last
mode selected. Range 0 to 2, default 0. See below.
•
Clear command:
clears one or all captures. Always returns 0.
See below
•
Reserved elements:
must be zero (0) on a write, returns 0.
Содержание 1404-M4
Страница 1: ...Bulletin 1404 Powermonitor 3000 1404 M4 1404 M5 1404 M6 1404 M8 User Manual Allen Bradley HMIs ...
Страница 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Страница 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Страница 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Страница 277: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 23 Ladder Diagram Allen Bradley HMIs ...
Страница 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Страница 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Страница 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Страница 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Страница 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Страница 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Страница 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Страница 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Страница 355: ...Allen Bradley HMIs ...