Publication 1404-UM001D-EN-E - October 2004
6-2
I/O Operations
Pulsed Control
Many electric energy meters provide a dry contact output that changes
state at intervals determined by a metered parameter.
Pulsed control
lets the Powermonitor 3000 emulate this function. You may select the
following options for the
Control source
parameter:
1 = Watt-hours forward
2 = Watt-hours reverse
3 = VAR-hours forward
4 = VAR-hours reverse
5 = VA-hours
6 = Ampere-hours
Set the
Output width
to the desired pulse duration in milliseconds. Set
this parameter to zero (0) if you want the output to toggle instead of
pulse. This operation emulates the KYZ operation of
electromechanical energy meters. For a two-wire KYZ connection, use
only one side of the relay. For a three-wire KYZ connection, use both
sides of the Form C output.
In a two-wire interface, (KY connection), an output event occurs only
when the output contact closes. In a three-wire connection, an event
occurs when either the KY or KZ contact closes. Therefore twice as
many output events occur in a three-wire connection as in a two-wire
connection for the same number of relay transitions.
Set the
Output scale
for the number of increments of the
Control
source
parameter it takes to pulse or toggle the selected output.
Follow these suggested steps to calculate the
output scale
:
1.
Determine the maximum value of the selected parameter
expected in an hour period. This is related to the feeder
capacity. For example, a 480 volt, 1200-ampere three-phase
feeder can supply approximately 100 kW or 100 kWh per hour.
2.
Divide this maximum parameter value by 3,600 to determine the
maximum value expected per second. In our example, we
round this to 280 Wh per second.
3.
Select a maximum pulse rate. This should be between 2 and 5
pulses per second for a two-wire KYZ connection and between
2 and 10 pulses per second for a three-wire connection. Let
’
s
use a three-wire KYZ connection and a pulse rate of 4 pps.
4.
Compute the output scale by dividing the result of (2) by the
result of (3) and rounding to the nearest integer. For our
example, we
’
ll set the output scale to 70.
Содержание 1404-M4
Страница 1: ...Bulletin 1404 Powermonitor 3000 1404 M4 1404 M5 1404 M6 1404 M8 User Manual Allen Bradley HMIs ...
Страница 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Страница 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Страница 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Страница 277: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 23 Ladder Diagram Allen Bradley HMIs ...
Страница 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Страница 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Страница 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Страница 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Страница 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Страница 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Страница 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Страница 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Страница 355: ...Allen Bradley HMIs ...