YP5000 Soft Starter User Manual
V1.0
Example:
Read Status Register Code 02 03 00 02 00 01
If the starter is starting up, return code 02 03 02 00 01
If the starter fails, return code 02 03 02 00 08, and can read the fault type, read the
type of failure.
This value maps the three-phase actual current average value of the motor * 10
(contains a fraction).
Example: read current value
Send code 02 03 00 02 00 01
If the current is 235A, return 02 03 02 09 2E (return value / 10 for the actual current
value).
40003 Current average value (hexadecimal)
When the status register 40002 bit 3 is 1, it indicates that the soft start is in a fault
mode. The fault code is consistent with 6.1.
Example: send code 02 03 00 04 00 01
If it returns 02 03 02 00 04, it indicates that the current input is missing (fault code
04).
40004 Fault code (hexadecimal)
40256-4027 is for the function register, the corresponding address is 0X0100-
0X0112, high byte address is 01, low byte address is 0X00-0X12, the
corresponding function code can be read and written. The following examples
illustrate their usage:
Example 1: The size of the read function code F5 (current limit)
Send code 02 03 01 05 00 01
Returning F5 function code to 02 03 02 01 5E indicates that the
current limit is 350%.
Example 2: Read function code FA (protection level)
Send code 02 03 01 0A 00 01
Returns the value of the read FA function code to 02 03 02 00 03,
reading the protection level 3.
Soft starter function parameter register40XXX
-37-