YP5000 Soft Starter User Manual
V1.0
Ø
Primary protection prohibits the external momentary terminal function, while
retaining only overheating, short circuit and start the input phase protection,
suitable for unconditional emergency start occasions, such as fire pumps.
Ø
Light load, standard, overload three protection levels with full protection, the
difference is that the motor overload thermal protection time curve is
different. Motor thermal protection standards are more stringent, and other
protection function parameters are the same as standard protection settings.
Operating over-load
protection level
Startup over-current
protection time
IEC60947-
4-2 standard
Use F6 to set
5 times of the
starting current
the data in the
table is typical
value
operating
overload
trip time
list
current
multiple
rip
time(s)
5
7.5
no
no
second level
10 level
20 level
10 level
3S
15S
30S
15S
3
4
5
3
3
3
3
4
4
4
4
5
5
5
4.5 2.3 1.5 23 1.2 7.5 46
23
15 4.5 2.3 1.5 23 12
FA code setting
specs
junior
1
( light load)
2
(standard)
3
(overloading)
4
( senior)
Ø
The code should be set according to the rated current value on the motor
plate. Otherwise, the starting current and the protection current will be greatly
deviated.
Ø
Code meter The motor current set by FP can not be less than 20% of the
nominal current of the soft starter. When the motor code set by the code FP is
small, the sensitivity error of the protection trip action will increase.
-24-