background image

 

- Instructions for use and maintenance issued by the manufacturer of the stove (if such instructions are not provided with 

the stove),  

- The documentation necessary to comply with the existing standards.                                             
    

 

INSTALLATION – STOVE INSTALLATION  

 
Responsibility for the work carried out at the place of connection is entirely on the user.
  
Before one turns the stove on, the installer must meet all legal standards of safety, as well as the following requirements:  
- to check that setting up the stove complies with local, national, and European regulations,  
- that the location of setting up the stove meets the requirements set forth in this manual,  
- to set up the flue pipes,  
- that air intake matches the type of the installed stove,  
- that the electrical connections are not set up using temporary and/or not insulated electrical cables,  
- to evaluate the effectiveness of grounding electrical systems,  
- to always use personal protective equipment and all means of protection that are prescribed by local regulations,  
- to always provide sufficient service space required for any maintenance and repair of stoves  
 

 

INSTALLING THE STOVE  

We recommend you to unpack the stove only when the stove is set up in the position where it will be connected.  
The stove is on the plastic pins that have M10 bolts (4 items), that are threaded into the stove base. At the screws there 

are M10mm threaded nuts to the plastic parts. The legs are wound up all the way to the base of the stove. After unpacking the 
stove, when you put it in a place where it will be located, it is necessary to unscrew all the legs, so that a total height from the 
floor to the base of the stove is about 25mm. When you are done with nivelation of the stove that needs to stand horizontally, 
tighten the nuts with a 17 wrench, which needs to approach the base of the furnace, and at the same time hand-holding the 
plastic part of the legs, tighten the nut. The height of about 25mm from the floor to the base is needed for better circulation of 
air and cooling the stove. In this way you protect the stove from overheating and you extend its life.  

If the surrounding walls and/or floors are made of materials that are not resistant to heat, then one should use adequate 

protection using the insulating material that does not burn.  
In order to protect the building construction against the risk of fire, flammable elements (such as walls, doors, furniture, home 
appliances…)
 must be kept on the safe distance from the stove: 100 mm from the rear side, 200 mm from the lateral sides and 
800 mm from the front side. Always leave at least 100 mm between the rear side of the stove and the wall to allow for proper 
air circulation, or for the air to flow properly in that area. To protect the floor if it is made of combustible materials (wood, 
parquet, linoleum, laminates, carpets…), we suggest you put a metal plate under the stove on the floor with the thickness of 3-
4 mm that will stretch 300 mm in front of the stove. Any elements made from wood (e.g. beams) or other combustible material 
located near the stove

 

should be protected/covered with fireproof material. 

        Leave enough clearance for maintenance work. 

     

If the stove is installed in a kitchen with a trellis for drawing out air or if it is placed in the room with appliances that use 

solid fuel (such as a wood burning stove), always make sure that the amount of inlet air in the room is sufficient to ensure safe 
operation of the stove. 

 

If a smoke channel goes through the ceiling, it should be properly thermally insulated using the protection out of insulating 

materials that does not burn. When the stove is set up into place, it should be levelled using pins.  

DANGER !  
The exhaust gas Armour must not be connected to:  
- the smoke pipe used by another heat generator (boilers, furnaces, fireplaces, stoves, etc.),  
- the air drawing system (grilles, ventilation openings, etc), even if the system is inserted into the drain pipe.  
DANGER !  
It is forbidden to install shut-off valves for the flow (draft) of air (flap valves that can prevent airflow or disable drafts).  
ATTENTION  
If the ejection path of smoke creates such a bad draft, of a bad flow of air (many curves, improper completion of the ejection 

of smoke, constriction, etc.) discharge of smoke can be bad, or in a situation like this smoke discharging is not as good as it 
could be.  

The smoke ejection system from the stove operates under negative pressure in the stove chamber and with mild pressure 

from the  smoke drain pipe. It is very important that the smoke extraction system is hermetically closed (sealed). This requires 
the use of a smooth tube on the inside. First of all you must carefully study the plan and structure of the room when the smoke 
extraction pipe is set up through the walls and roof, so that the installation of pipes is performed properly in accordance with 
the standards of fire protection.  

You  should  first  ensure  that  the  room  where  the  stove  is  located  has  enough  air  for  combustion.  It  is  advisable  to 

periodically performs check so as to ensure that the combustion air comes right up to the combustion chamber. The stove 
operates at 230 V  ~ 50 Hz. Make sure that the electrical cord is not underneath the furnace, to be away from the stove, to be 
away from hot spots, and not to touch any sharp edges that it could interdict. If the stove is electrically overloaded, this can 
lead to shortening of the lifetime of the electronics of the stove.  

Never turn off the power supply by pulling the plug when there is a burning flame in the stove. This could jeopardize the 

proper functioning of the stove.  

 

 

THE SMOKE EXHAUST SYSTEM   

The smoke exhaust must be carried out in accordance with existing standards. Exhaust gas tube should be well sealed 

(see Figures 1-7).  

For smoke exhaustion, one can also use classic brick chimneys while flues can also be made of pipes that need to be well 

insulated (double wall) and sealed, to avoid creating condensation in them. 

The drain tube absolutely must not be connected to other systems of any kind, such as the systems where the smoke is 

removed from the combustion chamber, exhaust grilles or air distribution system, etc. Also, the smoke exhaust must not be 

Содержание DINO 27

Страница 1: ...uel from timber biomass biofuels INSTRUCTIONS FOR CONNECTING OPERATION AND MAINTENANCE OF THE STOVE This product meets the requirements of the Ecodesign Directive in terms of efficiency and air pollut...

Страница 2: ...bustion of the pellet in the stove emits the same amount of carbon dioxide CO2 which would be freed as a result of the natural decay of wood The amount of carbon dioxide CO2 obtained through combustio...

Страница 3: ...g h 11 Degree of efficiency at maximum power 93 5 12 Minimum stove power radiation of water included 8 4 kW 13 Radiation stove power at minimum power 1 kW 14 The power of a water heater at minimum pow...

Страница 4: ...NG AND MAINTENANCE for employees who do maintenance 10 SPECIAL MAINTENANCE 10 IMPORTANT SAFETY INFORMATION 10 THE PELLET QUALITY IS VERY IMPORTANT 11 STORING THE PELLET 11 CONNECTING THE HYDRAULIC INS...

Страница 5: ...rd This is because the brunt of the stove is forward During transportation of the stove which has to be completely safe make sure that the forklift has the load that is greater than the weight of the...

Страница 6: ...wood e g beams or other combustible material located near the stove should be protected covered with fireproof material Leave enough clearance for maintenance work If the stove is installed in a kitc...

Страница 7: ...o 15 x 15 cm or a diameter of up to 15 cm and if there is a cover for checking and cleaning If the chimney has a larger cross section than 15x15cm or a diameter greater than 15cm a possible increased...

Страница 8: ...r cleaning the ashes is completely sealed and to seal it after each cleaning Please make sure everything is properly returned to its place and check the condition of the seals Figure 2a Cleaning eleme...

Страница 9: ...id for cleaning plug in SMER DIMA NE DA Figure 7 Mounting the flue pipe Insulation thickness mm Diameter of the smoke exhaust pipe mm D 80 D 100 Diameters of the holes holes to be made mm The walls ar...

Страница 10: ...This hole must be made on the outer wall of the room where the stove is located The supply of combustion air from the garage a warehouse for combustible materials or from a room where there are risks...

Страница 11: ...uld be cold and that the ashes should be cold as well They need to make sure the handles are cold as well NEVER TURN THE STOVE ON if there is just one of the safety devices that is defective improperl...

Страница 12: ...sive cleaners for cleaning the surface of the stove ROUTINE CLEANING AND MAINTENANCE DONE BY THE USER OF THE STOVE Use a drum shaped vacuum cleaner that can facilitate cleaning the stove The vacuum cl...

Страница 13: ...pulling the mechanism button a few times back and forth you will clean the chamber Do not worry if the mechanism moves slowly if it scratches or gets caught This is how it cleans the chamber Clean th...

Страница 14: ...er burning two tons of pellets Make sure the stove and the ash are cool The smoke channel chimney is resistant to wind and has to be checked and cleaned every year best at the beginning of the heating...

Страница 15: ...poor performance of the stove in case of use of the pellets of inappropriate quality STORING THE PELLET The pellets must be kept in a dry place that is not very cold Cold and moist pellets at the temp...

Страница 16: ...e looking at the stove The output safety valves whose connection protrudes through the rear wall above the pressure line should be put into the sewer pipes CIRCULATION PUMP A high quality Wilo RS 25 6...

Страница 17: ...out water It must be tied to the installation to which the consumers are connected radiators with minimum power of 8 kW PRACTICAL INSTRUCTIONS AND TIPS FOR THE USE OF THE HEATING SYSTEM All connection...

Страница 18: ...etting up and use simple and direct user functions reliable and flexible functional software specially developed for pellets burning appliances advanced features available to installers for adapting s...

Страница 19: ...oes into Standby mode LED symbols Igniter LED is on Igniter is on Auger LED is on Auger is active Pump LED is on Pump is active L3 Aux 1 output LED is on Aux 1 output is activated L4 Additional engine...

Страница 20: ...till in the ignition stage The system will stop working only when it enters the Run Mode Link Error This message informs you that there is no communication between the LCD display and the controller o...

Страница 21: ...buffer and other heating parameters Chrono Menu for selecting chrono program mode and boiler on off times Manual Load Menu for manual loading of the auger It is only feasible when the system is in the...

Страница 22: ...alues of the fan speed of the flue gas fans will be increased by 15 compared to the factory values Factory settings U03 1000 U04 1200 U05 1400 U06 1600 U07 1800 U11 900 Calibrated values U03 1150 U04...

Страница 23: ...e stove is set for precisely determined periods of time It contains two submenus Modality Programming Modality By entering the Chrono menu two submenus appear namely Modalities and Programming Via P4...

Страница 24: ...s that can be chosen Daily program the week day is selected and the system on and off times are programmed There are three time ranges for each day Weekly program system on off times are programmed fo...

Страница 25: ...n 3 seconds After that you can find the following functional conditions of the stove Check Up In the check up stage the initial check of the input signals of the stove and the correctness of the probe...

Страница 26: ...set water temperature it goes into modulation and continues to increase the water temperature by inertia up to the value 4 C higher than the set water temperature in the boiler 2 When an external roo...

Страница 27: ...for more than 3 seconds Contact a service Flue gas fan works at speed different than set Er11 Clock error Problems with internal clock Press and hold the P2 button for more than 3 seconds Check the ac...

Страница 28: ...itch on the back side of the stove and on the control panel the motherboard FLUE GASES FAN If the fan stops the motherboard immediately blocks the supply of pellets and an alarm signal will show GEAR...

Страница 29: ...throwing away or disposing of an old used stove is the sole responsibility of the owner The owner of the stove must abide by the regulations in his her country related to the safety and environment p...

Страница 30: ...was due to too much or too low voltage as well as due to force majeure Malfunctions of the appliance can be removed outside the warranty period with original spare parts that we also give a warranty f...

Отзывы: