Ignition – Fixed Stage 
This stage is a fixed time period of 180 seconds and in case the conditions for stove ignition are reached before the end of this 

stage, it will always last until the stove is switched to the stabilization stage only after the expiration of a fixed period of time. At 
this stage, the igniter, auger and flue gas fan are active. 

 

Ignition – Variable Stage 
This stage occurs after a fixed ignition stage. The duration of this stage is a variable time period that lasts up to the moment 

when the ignition conditions are met, or until the flue gas temperature has reached at 45°C. When the conditions for igniting the 
boiler is met before the end of this stage, it is interrupted and the next stage - the stabilization stage starts. At this stage, the igniter, 
auger and flue gas fan are active. 

 

Stabilization 
The stabilization stage is a transient state between the ignition stage and the stage of operation. This stage occurs when the 

ignition condition is met, i.e. when the flue gas temperature reaches 45°C. It lasts for three minutes and during this time the auger, 
flue gas fan and igniter are active. 

 

Run Mode 
After the stabilization stage, the stove operation stage starts. At this stage, there are five power levels that can be adjusted. At 

this stage, the igniter is switched off while the auger, flue gas fan and pump are active and operate at different intensities depending 
on the power level of the stove. The stove works at a given power until the modulation conditions are met. 

 

Modulation 
The stove goes into the state of modulation when one of the three conditions is fulfilled: 

1.

 

When the stove reaches the set water temperature 

2.

 

When the stove reaches the set ambient temperature 

3.

 

When the flue gas temperature reaches a value greater than 200°C 

In the state of modulation, the stove works at minimum power - power 1, until the temperature decreases below the limit value. 
 

 

Standby 
The stove goes into Standby when one of the two conditions is met: 
1. When the boiler reaches the set water temperature, it goes into modulation and continues to increase the water temperature 

by inertia up to the value 4°C higher than the set water temperature in the boiler. 

2. When an external (room) thermostat is responding 
In Standby mode, the pellets insertion stops and the stove is switched off. The stove is  switched on again when the water 

temperature in the boiler is reduced by 4°C below the set value or when the room thermostat is deactivated. 

 

Safety 
Safety state occurs when the flue gas temperature exceeds 230°C and when the water temperature in the boiler reaches 85°C. 

At this stage, pellets insertion stops until the flue gas temperature is below 230°C or the water temperature in the boiler is below 
85°C. If the temperature is not reduced in the next 60 seconds, the boiler goes into the Alarm state and sends the  Er04 or Er05 
message.  

 

Extingushing 
The stove is switched off by pressing the P2 button for more than 3 seconds. 
Then an extinguishing stage occurs in which the 

insertion of pellets is stopped and the flue gas fan and pump work at the maximum capacity in order to cool the boiler down as 
soon as possible. The minimum duration of the extinguishing stage is 300 seconds, and the condition for switching off the stove 
completely is when the flue gas temperature is less than 70°C. 

 

OFF 
In this state, the stove is switched off, i.e. no outlet on the stove (flue gas fan, pump, igniter and auger) is not active. 

 

Block 
The Block state occurs in the event of an error or an alarm. In the Block state, the exhaust fan, the auger and the igniter are off. 

Hold down the P2 button for 3 seconds to exit: if there are no more block conditions or there is no cause of alarm, the system will 
turn off. 

 

Recover Ignition 
The stove goes into this stage in two cases: 

1.

 

If the power supply is interrupted during the operation and the flue gas temperature is greater than 45°C. 

2.

 

Pressing the main switch at the moment the stove is in the extinguishing stage.   

 

 

 

POSSIBLE PROBLEMS AND SOLUTIONS 

 

Message on 

display 

Description 

Possible causes 

Resetting the error 

Possible  solutions  to  the  cause 

of the alarm 

 
 

 
 

 

Wait  until  the  stove 

completely 

cools 

Check  the  correctness  and 

functionality of the pump 

Содержание DINO 27

Страница 1: ...uel from timber biomass biofuels INSTRUCTIONS FOR CONNECTING OPERATION AND MAINTENANCE OF THE STOVE This product meets the requirements of the Ecodesign Directive in terms of efficiency and air pollut...

Страница 2: ...bustion of the pellet in the stove emits the same amount of carbon dioxide CO2 which would be freed as a result of the natural decay of wood The amount of carbon dioxide CO2 obtained through combustio...

Страница 3: ...g h 11 Degree of efficiency at maximum power 93 5 12 Minimum stove power radiation of water included 8 4 kW 13 Radiation stove power at minimum power 1 kW 14 The power of a water heater at minimum pow...

Страница 4: ...NG AND MAINTENANCE for employees who do maintenance 10 SPECIAL MAINTENANCE 10 IMPORTANT SAFETY INFORMATION 10 THE PELLET QUALITY IS VERY IMPORTANT 11 STORING THE PELLET 11 CONNECTING THE HYDRAULIC INS...

Страница 5: ...rd This is because the brunt of the stove is forward During transportation of the stove which has to be completely safe make sure that the forklift has the load that is greater than the weight of the...

Страница 6: ...wood e g beams or other combustible material located near the stove should be protected covered with fireproof material Leave enough clearance for maintenance work If the stove is installed in a kitc...

Страница 7: ...o 15 x 15 cm or a diameter of up to 15 cm and if there is a cover for checking and cleaning If the chimney has a larger cross section than 15x15cm or a diameter greater than 15cm a possible increased...

Страница 8: ...r cleaning the ashes is completely sealed and to seal it after each cleaning Please make sure everything is properly returned to its place and check the condition of the seals Figure 2a Cleaning eleme...

Страница 9: ...id for cleaning plug in SMER DIMA NE DA Figure 7 Mounting the flue pipe Insulation thickness mm Diameter of the smoke exhaust pipe mm D 80 D 100 Diameters of the holes holes to be made mm The walls ar...

Страница 10: ...This hole must be made on the outer wall of the room where the stove is located The supply of combustion air from the garage a warehouse for combustible materials or from a room where there are risks...

Страница 11: ...uld be cold and that the ashes should be cold as well They need to make sure the handles are cold as well NEVER TURN THE STOVE ON if there is just one of the safety devices that is defective improperl...

Страница 12: ...sive cleaners for cleaning the surface of the stove ROUTINE CLEANING AND MAINTENANCE DONE BY THE USER OF THE STOVE Use a drum shaped vacuum cleaner that can facilitate cleaning the stove The vacuum cl...

Страница 13: ...pulling the mechanism button a few times back and forth you will clean the chamber Do not worry if the mechanism moves slowly if it scratches or gets caught This is how it cleans the chamber Clean th...

Страница 14: ...er burning two tons of pellets Make sure the stove and the ash are cool The smoke channel chimney is resistant to wind and has to be checked and cleaned every year best at the beginning of the heating...

Страница 15: ...poor performance of the stove in case of use of the pellets of inappropriate quality STORING THE PELLET The pellets must be kept in a dry place that is not very cold Cold and moist pellets at the temp...

Страница 16: ...e looking at the stove The output safety valves whose connection protrudes through the rear wall above the pressure line should be put into the sewer pipes CIRCULATION PUMP A high quality Wilo RS 25 6...

Страница 17: ...out water It must be tied to the installation to which the consumers are connected radiators with minimum power of 8 kW PRACTICAL INSTRUCTIONS AND TIPS FOR THE USE OF THE HEATING SYSTEM All connection...

Страница 18: ...etting up and use simple and direct user functions reliable and flexible functional software specially developed for pellets burning appliances advanced features available to installers for adapting s...

Страница 19: ...oes into Standby mode LED symbols Igniter LED is on Igniter is on Auger LED is on Auger is active Pump LED is on Pump is active L3 Aux 1 output LED is on Aux 1 output is activated L4 Additional engine...

Страница 20: ...till in the ignition stage The system will stop working only when it enters the Run Mode Link Error This message informs you that there is no communication between the LCD display and the controller o...

Страница 21: ...buffer and other heating parameters Chrono Menu for selecting chrono program mode and boiler on off times Manual Load Menu for manual loading of the auger It is only feasible when the system is in the...

Страница 22: ...alues of the fan speed of the flue gas fans will be increased by 15 compared to the factory values Factory settings U03 1000 U04 1200 U05 1400 U06 1600 U07 1800 U11 900 Calibrated values U03 1150 U04...

Страница 23: ...e stove is set for precisely determined periods of time It contains two submenus Modality Programming Modality By entering the Chrono menu two submenus appear namely Modalities and Programming Via P4...

Страница 24: ...s that can be chosen Daily program the week day is selected and the system on and off times are programmed There are three time ranges for each day Weekly program system on off times are programmed fo...

Страница 25: ...n 3 seconds After that you can find the following functional conditions of the stove Check Up In the check up stage the initial check of the input signals of the stove and the correctness of the probe...

Страница 26: ...set water temperature it goes into modulation and continues to increase the water temperature by inertia up to the value 4 C higher than the set water temperature in the boiler 2 When an external roo...

Страница 27: ...for more than 3 seconds Contact a service Flue gas fan works at speed different than set Er11 Clock error Problems with internal clock Press and hold the P2 button for more than 3 seconds Check the ac...

Страница 28: ...itch on the back side of the stove and on the control panel the motherboard FLUE GASES FAN If the fan stops the motherboard immediately blocks the supply of pellets and an alarm signal will show GEAR...

Страница 29: ...throwing away or disposing of an old used stove is the sole responsibility of the owner The owner of the stove must abide by the regulations in his her country related to the safety and environment p...

Страница 30: ...was due to too much or too low voltage as well as due to force majeure Malfunctions of the appliance can be removed outside the warranty period with original spare parts that we also give a warranty f...

Отзывы: