15.3.6.
REMOTE CONTROL MENU
This menu allows you to activate or deactivate the remote control - Remote Control SYTX. Remote control is
not provided as factory setting.
15.3.7.
LANGUAGE SELECTION MENU
This menu allows you to change the language on the LCD display.
15.3.8.
DISPLAY MENU
Menu
Description
Set contrast
Menu for setting contrast on the LCD display
Set Minimum Light
Menu for setting brightness on the LCD displeja
Setting Contrast
Via P4 and P6 buttons contrast is increased or decreased.
By pressing the P3 button, the changes are saved and one can exit the menu.
Via P1 button one can exit the menu without saving the changes.
Set Minimum Light
Via P4 and P6 buttons brightness is increased or decreased (min 0, max 20).
By pressing the P3 button, the changes are saved and one can exit the menu.
Via P1 button one can exit the menu without saving the changes.
15.3.9.
SYSTEM MENU
This menu allows access to technical settings. Access is password protected and allowed only to authorized technical
staff.
STOVE IGNITION AND FUNCTIONAL CONDITIONS
The stove is switched on by pressing the P2 button for more than 3 seconds. After that you can find the following functional
conditions of the stove:
Check Up
In the check up stage, the initial check of the input signals of the stove and the correctness of the probes is performed. At this
stage, the flue gas fan runs at the maximum speed and the auger and igniter are switched off. The check up stage takes a few
seconds and after a successful check, the ignition stage starts.
Ignition
The ignition stage consists of the following four sub-stages:
- Preheating stage
- Pellet preloading stage
- Fixed ignition stage
- Variable ignition stage
For the entire duration of the ignition stage, the IGNITION message is shown on the display. There are no special tags for sub-
stages.
Ignition Preheating
At this stage, the igniter is started before the pellets inserting starts. In order to make burn the pellets as efficient as possible,
it is desirable that the igniter is already heated at the moment when the pellets inserting starts. At this stage, the igniter is active
and the auger is inactive. The flue gas fan runs at a lower speed to accelerate the ignition of the igniter.
Ignition Preload
At this stage, the initial insertion of pellets occurs, i.e. the auger inserts a certain quantity of pellets that is necessary for ignition.
At this stage, the igniter, auger and flue gas fan are active.