14.3.1.1 COMBUSTION POWER
Menu for setting the system's combustion power in manual or automatic mode (if available). In manual mode, the user can
adjust the desired combustion power by himself.
Combustion
Description
1-5 (Combustion power 1, 2, 3, 4 i 5)
Power is set manually by selecting Power 1, 2, 3, 4 or 5.
Auto
Power is set automatically by the system
The Combustion Power menu is entered by pressing the P3 button.
The desired combustion power is selected via the P4 and P6 buttons. Press the P3 button to save the newly set value of the
parameter. To cancel all modifications and return to the old values, press the P1 button.
14.3.1.2 COMBUSTION RECIPE
Menu for selecting the combustion recipe. If only one recipe is set at the factory, this menu is not visible.
14.3.1.3 AUGER CALIBRATION
Menu for changing the feeding rate of the auger. The system has 10 calibration steps (from -5 to +5, the factory default is 0).
The calibration effect is valid in the operating mode and in the modulation. For each step, the value is increased or decreased by
5%.
Example: Calibration value = -2; (-2*5% = -10%) - means that the calibrated values of the auger speed will be reduced by 10%
compared to the factory values.
Factory settings
C03=60
0
C04=90
0
C05=120
0
C06=160
0
C07=200
0
C11=600
Calibrated values
C03=54
0
C04=81
0
C05=108
0
C06=144
0
C07=180
0
C11=540
14.3.1.4 COMBUSTION FAN CALIBRATION
Menu for changing the number of revolutions of the flue gas fan. The system has 10 calibration steps (from -5 to +5; the
factory default is 0). The calibration effect is valid in the operating mode and in the modulation. For each step, the value is
increased or decreased by 5%.
Example: Calibration value = +3; (+3*5% = +15%) - means that the calibrated values of the fan speed of the flue gas fans will
be increased by 15% compared to the factory values.
Factory settings
U03=1000
U04=1200
U05=1400
U06=1600
U07=1800
U11=900
Calibrated values
U03=1150
U04=1380
U05=1610
U06=1840
U07=2070
U11=1030
Note: The calibration of the auger and flue gas fan must not be performed without prior consultation of an authorized service
or representative of the manufacturer.
14.3. 2.
HEATIN G MA NAGE MENT MENU
This is a menu for modifying parameters that determine the heating performance of the boiler. It contains several submenus.
The menu is accessed by pressing the P3 button and the following submenus appear: