31481875EN-00
24
Alfa LU-VE is a trademark registered and owned by LU-VE Group.
Alfa LU-VE reserves the right to change specifications without prior notification.
SF31MC
n. of fans
coil type
Electric defrost in coil (E)
Driptray heater (HD)
n.
W (x1)
W tot
n.
W tot
1
1
2
850
1700
1
235
2
3
850
2550
1
235
2
1
2
1450
2900
1
415
2
3
1450
4350
1
415
3
1
2
2025
4050
1
600
2
3
2025
6075
1
600
4
2
3
2600
7800
1
775
n. of fans
Fan shroud heater (FRH)
n.
W (x1)
W tot
1
1
145
145
2
2
145
290
3
3
145
435
4
4
145
580
In case one or more options are mounted, the total power consumption is the sum of each con-
sumption.
6.12 Defrost connections (SF31MC models - optional)
Ensure complete electrical isolation before performing any wiring.
Содержание Optigo SFMC