2.3 Options
• Electric defrost in coil (E)
For cold rooms with room temperatures below 4 °C frost build-up is likely, the application of a
defrosting system is recommended. The stainless steel defrost elements are connected to
dedicated terminal box.
• Driptray heater (HD)
• Electric defrost in coil + Driptray heater (E+HD)
Model
Fin spacing
N
E
HD
E+HD
F27MC
all
standard
✓
✓
✓
F31MC
4.5, 6
standard
✓
✓
✓
F31MC
7, 9
standard
n.a.
n.a.
✓
F35MC
all
standard
n.a.
n.a.
✓
•
Coil protection: pre-coated aluminium fins (AP)
• EC fan motors: single speed for F27MC, dual speed for F31MC and F35MC
• Central internal connection box wired to a single external switch (SW)
• Fan shroud heater (FRH)
• Driptray insulation (IS)
• Shut-up sock with adapter ring - only for F31MC and F35MC models
• Insulated suction hood
2.4 Code description
F27MC E A - 2 1 - 4
N
* AL BP - * FRH
1
2
3
4
5
6
7
8
9 10
11
12
1
Optigo FMC cubic commercial unit coolers
(F27MC=Ø 275 mm, F31MC=Ø 315 mm, F35MC=Ø 350 mm)
2
Refrigerant system (E=HFC, X=CO
2
, W=brine)
3
Fan motor type (A=AC, E=EC)
4
Number of fans (1 to 4)
5
Coil type (1, 2)
6
Fin spacing (4=4.5, 6=6.0, 7=7.0, 9=9.0 mm)
7
Defrost system (N=air defrost, E=electric defrost in coil, HD=driptray heater,
E+HD=electric defrost in coil+driptray heater)
8
Circuits code - only for brine units
9
Fin material (AL=aluminium, AP=pre-painted aluminium)
10
Packing (BP=box+pallet, CR=crate)
11
Applications - only for CO
2
units (blank=DX 60 bar design pressure, P=pumped 60 bar,
85=DX 85 bar design pressure)
12 Options