Mount the outdoor temperature sensor (option) on the north side of the building,
2 metres above the ground, or higher.
See
2.12 Installing the outdoor temperature sensor.
•
Connect the non-polarity cable from outdoor temperature sensor to the electric box.
Carefully press the cable into the trail in the insulation.
•
Connect the correct power cable to connection box and press it into the trail in the
insulation.
•
Place the lid over the connection box.
•
Put the electrical cable into a wall outlet.
See
2.13 Starting up sequence for AL Mini City with component check
•
Mount the two insulation covers. Start with the top that covers the substation. Always
use the handles on the side when handling the cover
Mounting options
2.8
•
If the substation is connected to a low temperature system, for example floor heating,
a safety thermostat must be mounted and activated before start up.
For more information see manual
Installation Service And Operating Instruction AL Mini City
on
http://www.alfalaval.com/minicity
.
Commissioning advice AL Mini City
2.9
•
Adjust the hot water temperature by having a hot water tap open at normal flow rate.
Measure the temperature at the draw-off point with a thermometer. It takes about 20
seconds to get a stable tap water temperature.
The temperature should be approximately 50°C.
Alfa Laval recommends that the primary inlet temperature is at least 10º higher than
the tap water temperature.
NOTE
: Make sure that no cold water is mixed with the hot water while making this
adjustment.
Seal the hot water valve with the provided strap.
•
The room thermostat has been pre-set at the factory to use control mode; Outside
Temperature Control (OTC control).
To change control mode
see 3 Room thermostat T87C2073
General adjustments and settings
2.10
The property owner must be instructed in the operation, setting and care of the unit.
It is particularly important to provide information about the safety systems and about
hazards that may arise in relation to the high pressure and temperature of the primary
heating water.