ZRT-R

®

AIRFLOW & ZONE CONTROL

ZONE REGISTER TERMINAL

Description                                                 

ALDES patented* Zone Register Terminals (ZRT®) are 

designed to introduce flexibility and dynamic control to 

central ventilation systems. Used in residential applications, 

the ZRT® zonally regulates ventilation where it is required 

without the need for individual fans. Each ZRT® is a 

combination grille, register box, and control damper. 

To ensure the proper operation of the damper assembly, 

do not exceed 1.0 in. w.g. of differential pressure across the 

damper door. ZRT® 6" supply models require a minimum 

flow constant airflow regulator.

By replacing static grilles in large central systems, the ZRT-1 

model provides on-off control for on-demand ventilation. 

This allows central fan downsizing and promotes energy 

savings by minimizing necessary fan horsepower and 

ventilation-induced heat and cooling loads on the home. 

The ZRT-2 model can be used for combination low-flow 

indoor air quality ventilation and on-demand high-flow 

spot ventilation using the same central fan system. This 

is achieved by integrating a minimum constant airflow 

regulator directly into the damper sub-assembly. With the 

damper completely closed, the constant airlfow regulator 

will allow steady, low-continuous ventilation during fan 

operation. When other terminals are opened for on-

demand control of spot ventilation, the closed ZRT-2 will 

maintain the set low-continuous rate through the constant 

airflow regulator minimum flow control. By opening the 

ZRT-2’s control damper, the low-flow regulator is removed 

from the air stream, allowing unrestricted maximum-boost 

ventilation.

Airflow rate can be set or adjusted by rotating the dial 

from either side. The airflow indicator will move to show 

the selected CFM. The airflow label has multiple defined 

setpoints, but the unique adjustment mechanism of the 

CAR3 allows for infinite adjustability between the minimum 

and maximum limits.

The ZRT® can activate fans used in central ventilation 

systems. Through the use of an integral damper end-switch, 

the ZRT® can trigger the remote fan to start. This provides 

the distinct advantage of allowing the fan to only ventilate 

specific spaces when called upon, without the need for 

separate fans in each space. This is especially important 

in residential bath applications using popular in-line and 

multi-port fans, where low noise and a single exterior vent 

penetration are desired.

IOM

ZRT-1 MODEL                      ZRT-2 MODEL

*U.S. Pat. No. 7,766,734

Mounting                                                 

The ZRT® is available with mounting brackets to accommodate 

new or existing construction. Spanner brackets that allow 

mounting to joists up to 16" on center are provided and should 

be secured using the screws provided (See Figure 1). Install 

additional blocking or use a single joist bracket if spacing is 

greater than 16" on center. 

Wiring                                                         

The ZRT® is available with 24 VAC or 120 VAC actuator motors. 120 

VAC wiring options are shown in Figures 2-4, and 24 VAC wiring 

options using the Zone Terminal Fan Control Center (Model ZTC) 

are shown in Figures 5 and 6.

Damper

Assembly

Grille (Included)

Integral CAR3 Minimum 

Flow Regulator and Damper

16” o.c. 

Mounting 

Brackets 

(Included)

CAR3

Maximum

Flow Regulator

(Optional)

(Not Shown)

CAR3

Maximum

Flow Regulator

(Optional)

Damper

Motor

Cover

Содержание ZRT-R Series

Страница 1: ...l damper the low flow regulator is removed from the air stream allowing unrestricted maximum boost ventilation Airflow rate can be set or adjusted by rotating the dial from either side The airflow ind...

Страница 2: ...and comfort of the occupants as well as an investment in the protection of the building from the damaging effects of excessive indoor humidity 6 Installation work and electrical wiring must be done b...

Страница 3: ...ontrol each ZRT and fan in this configuration Continuous fan operation using 120 VAC power supply to ZRT 2 terminals The fan and ZRT terminals may be wired independently Intermittent fan operation usi...

Страница 4: ...er and ZRT 1 terminals SPST convenience switches such as manually operated mechanical timers or dehumidistats may be used to control each ZRT and fan in this configuration The fan is controlled by the...

Страница 5: ...www aldes na com CAR3 Constant Airflow Regulator Installation Operation Maintenance EN...

Страница 6: ...airflow rates the minimum pressure required to achieve the selected airflow may exceed 0 12 in w g Each diameter has a unique range for both low and high pressure variants The CAR3 L low pressure is...

Страница 7: ...duct or duct collar with a flexible duct connector listed to UL 2043 the CAR3 must be inserted at least 1 2 times the duct diameter from the flexible duct and or duct connector Orient the CAR3 accord...

Страница 8: ...fan speed CAR3 damper not functioning properly Check CFM calibration on CAR3 Adjust to proper airflow value 4 MAINTENANCE WARRANTY The CAR3 needs no maintenance when used in normal conditions The add...

Отзывы: