Introduction

Description of Operation

3 Float: 

With both “HOA” switches in “Auto” and the pump selector switch in “ALT”: On water rise, the “off” float will 
close and when the level closes the “lead” float, pump 1 will start and pump down to the “off” float.  The 
panel will alternate so on the next cycle pump 2 will activate.  If the level reaches the “lag” float, both 
pumps and the alarm will activate and pump down to the “off” float. Alarm turns off at the “off” level.  For a 
pump up application the floats are reversed (see float configurations Fig. #A on page 4).

4 Float:

With both “HOA” switches in “Auto” and the pump selector switch in “ALT”: On water rise, the “off” float will 
close and when the level closes the “lead” float, pump 1 will start and pump down to the “off” float.  The 
panel will alternate so on the next cycle pump 2 will activate.  If the level reaches the “lag” float, both 
pumps will activate and pump down to the “off” float. If the reaches the “alarm” float the alarm will 
activate. Alarm turns off when the alarm float is “off”. For a pump up application the floats are reversed 
(see float configurations Fig. #B on page 4).

Before proceeding with the installation or operation of the control panel read all instructions thoroughly, 
as well as comply with all Federal, State and Local Codes, Regulations and Practices.  The control panel 
must be installed by qualified personnel familiar with all applicable local electrical and mechanical codes.  
Refer to the National Electrical Code (NFPA 70).  Failure to properly install and test this product can result 
in personal injury or equipment malfunction.  All conduit connected to the panel must be sealed with 
conduit sealant to prevent moisture or gases from entering the panel.  NEMA 1 enclosures are for indoor 
use only while NEMA 4X panel enclosures may be used indoor or outdoor.  Refer to panel model name-
plate on inside of door for enclosure rating. Note: If options are ordered that affect the number of floats, 
refer to the panel schematic for complete information.

Safety Guidelines

1.

 

DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE,                  

    ETC. DO NOT USE IN EXPLOSIVE

 

ATMOSPHERES.  CONTROL PANEL SHOULD ONLY BE USED IN  

    WATER AND WASTEWATER APPLICATIONS THAT ARE NOT RATED AS A HAZARDOUS LOCATION.

 

2.

 

DO NOT WORK ON THE CONTROL PANEL WITH LIVE VOLTAGE APPLIED TO THE CONTROL PANEL  

    WITH WET HANDS OR WHEN STANDING ON A WET SURFACE.

 

3.

 

DISCONNECT ALL ELECTRICAL SERVICE BEFORE WORKING ON OR HANDLING THE CONTROL                              

    PANEL

 

4.

 

INCOMING VOLTAGE MUST MATCH THE CONTROL PANEL VOLTAGE.  REFER TO THE PANEL SCHE- 

    MATIC FOR COMPLETE INFORMATION.

 