1665 DMX High-Capacity shelf installation
Equipment and cable installation for 1665 Data Multiplexer
(1665 DMX)
............................................................................................................................................................................................................................................................
365-372-304R7.1
Issue 1, November 2007
1 - 1 3
........................................................................................................................................................................................................................
5
Verify with an ohmmeter that the 1665 DMX High-Capacity shelf is grounded to the bay
frame. Measure between the 1665 DMX High-Capacity shelf mounting bracket and the
office ground lug on the bay frame.
Requirement:
The ohmmeter reads less than 1 ohm.
........................................................................................................................................................................................................................
6
If the Ohmmeter reading is not less than 1 ohm, a secondary ground should be used for
each shelf. Use an 8 AWG wire from the UL (Green M5 Screw) safety ground on the side
of the shelf to bay frame or office ground.
Important!
It is important to remove the paint in the area where the wire is to be
connected to the bay and to apply no-ox before connecting the wire.
........................................................................................................................................................................................................................
7
Check off the appropriate box in
Appendix E, “Installation checklist”
.
........................................................................................................................................................
E
N D
O
F
S
T E P S
Содержание Data Multiplexer Explore 1665
Страница 8: ... Contents v i i i 365 372 304R7 1 Issue 1 November 2007 ...
Страница 12: ... List of figures x i i 365 372 304R7 1 Issue 1 November 2007 ...
Страница 16: ... List of tables x v i 365 372 304R7 1 Issue 1 November 2007 ...
Страница 24: ... About this document x x i v 365 372 304R7 1 Issue 1 November 2007 ...
Страница 168: ... 1665 Data Multiplexer 1665 DMX stand alone installation tests I I 2 365 372 304R7 1 Issue 1 November 2007 ...
Страница 250: ... Additional optical tests optional Installation tests 4 6 2 365 372 304R7 1 Issue 1 November 2007 ...
Страница 272: ... Final operations Operational tests 5 2 2 365 372 304R7 1 Issue 1 November 2007 ...
Страница 274: ... 1665 Data Multiplexer 1665 DMX ring setup and testing I I I 2 365 372 304R7 1 Issue 1 November 2007 ...
Страница 326: ... Cleaning pluggable optics modules Fiber cleaning B 1 4 365 372 304R7 1 Issue 1 November 2007 ...
Страница 408: ...I N 4 365 372 304R7 1 Issue 1 November 2007 Index ...