Battery Reserve Times for batteries inside 60ECv2 battery
cabinet
Battery Reserve Times for battery strings inside 60ECv2 battery cabinet
The table below lists the Battery Reserve Times for 12IR145 battery strings inside the
60ECv2 battery cabinet. Various numbers of battery strings are connected in parallel. The
provided values are for battery strings powering a 10,500 watt load. One battery string
consists of two 12IR145 (145 Ah) batteries connected in series.
Battery Reserve Times for battery strings inside 60ECv2 battery cabinet powering 10,500 watt
load
(One string = Two 12IR145 (145 Ah) batteries connected in series)
Number
of battery
strings
con-
nected in
parallel
2
4
6
8
10
12
14
Battery
Reserve
Time
(Hours)
0.8
1.9
3.2
4.6
6.1
7.7
9.4
Electrical power requirements for 9927 Distributed Base
Station Outdoor Cabinet
Power requirements for 9927 Distributed Base Station
Outdoor Cabinet
Battery Reserve Times for batteries inside 60ECv2 battery
cabinet
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
8-12
Alcatel-Lucent – Proprietary
Use pursuant to applicable agreements
9927 Dist BTS Outdoor
401-703-516
Issue 1
March 2012