Installing Optional Sensors/Transducers
4200-088
12-2
Revision 1.03
Figure 33 - String Current Connection on Rear of UXSM or UXCM
12.2.
Float Current Transducer
A float current transducer can be used to measure very small charge currents. This option utilizes the
Float Current Charging Probe (FCCP) made by Multitel. Although the instructions below will show proper
connections to the BDSU systems, it is recommended to read the user’s guide provided with the unit to
better understand the requirements.
When installing this option, a specific harness will be included in the installation kit separate from the
FCCP packaging. One of two standard lengths supplied is the 1102-188-12 is a12’ cable and is typically
used in battery cabinet installations and the other is a 50’ cable, 1102-188-50 used for large cell count
flooded type battery installations.
Figure 34 - Float Current Connection Cable
On one end of the float current connection cable are two connectors that connect directly to the control
unit of the FCCP. Connect the power to the left most connector and the FCCP output to the analog
section of the connector array.