background image

I.

Model Numbers

8Ah Max

28.2VAC

1.25A

34Ah

4.0A

24VDC

PS5-24040-B03-CE

 01334

20Ah Max

17.5VAC

0.75A

34Ah

4.0A

12VDC

PS5-12040-B03-CE

 01332

8Ah Max

28.2VAC

1.25A

34Ah

2.5A

24VDC

PS5-24025-B03-CE

 01333

20Ah Max

17.5VAC

0.75A

34Ah

2.5A

12VDC

PS5-12025-B03-CE

 01331

Battery

Storage in

Cabinet

XFMR

Voltage

Maximum

AC Input

Current

Maximum

Battery

Capacity

System
Current

System
Voltage

Model Number

AS

Order

No.

II.

Installation Instructions

1. Mount cabinet per mechanical dimensions and knockout locations given in Section IV.
2. Connect 240VAC, 50Hz., single phase to the black and white leads of the transformer in  accordance

with local codes. 

3. Low Volt AC Input - Connected to secondary winding of the transformer.

v

 Fused at 10 Amps (Fuse Type AGC-10)

4. Verify output voltage at "DC Output" and "Battery" terminals.

12V system measures approximately 13.8VDC.
24V system measures approximately 27.6VDC.

5. Connect battery set to "Battery" terminals.

CAUTION: Observe polarity; incorrect polarity will destroy battery fuse.
Fused at 10 Amps (Fuse Type AGC-10).
Recommended battery type - PowerSonic (PSSeries) or YUASA (NPSeries) sealed lead acid/gel cell.

6. Connect "DC Output" to input of user system.

CAUTION: Observe polarity; incorrect polarity may damage user system.
Refer to Section I for Maximum Allowable System Current.
Output terminals are POWER LIMITED on version PS5-XX025-B03-CE
Output terminals are Nonpower limited on version PS5-XX040-B03-CE.

7. Visual Indicators:

AC Presence LED1:

Green LED

System OK     LED3:

Green LED

LED2 (Red LED) serves no user function.

8. Connect "Fault Output" to system fault annunciation.

Form "C" Relay Contacts rated 1 Amp @ 24VDC resistive
Relay Contacts labeled in the non-operational (fault) condition.
Fail-safe; active until an actual fault condition.

9. Fault Conditions:

Low AC / No AC / Blown AC Fuse / Low Battery / Blown Battery Fuse

CAUTION: Fault condition reporting may be delayed dependent on power supply loading.
The battery set is NOT supervised for presence.

10. Battery Standby Information:

a) For 60 hr. standby with 34Ah battery set - Max standby draw: .5A, Max 5 minute alarm current: 2A.
b) For 24 hr. standby with 34Ah battery set - Max standby draw: 1A, Max 5 minute alarm current: 2A.
c) For 4 hr. standby with 20Ah battery set - Max standby draw: 2.5A, Max 5 minute alarm current: 2.5A.

11. Power Supply System Draw (No AC, No load) is 25mA.

III.

Typical Hook-up Diagrams

            Power Supply/Battery Chargers

                      Installation Instructions

AlarmSaf

 

w

 

65A Industrial Way 

w

 Wilmington, MA 01887-3499 

w

 (978) 658-6717 

w

 FAX: (978) 658-8638  Web Site:  www.alarmsaf.com

52-008B
032497

AC FUSE  (AGC-10)

BATT FUSE  (AGC-10)

LOW

VOLT

AC

CONNECT

BATTERY

CONNECT

+

_

DC

OUTPUT

+

_

NC

C

NO

FAULT

OUTPUT

PS5 Board 

Input and Output Terminals

Low Volt AC Input Terminals

and Battery Terminals are

Nonpower-Limited

DC Output Terminals and Fault

Output Terminals are

 Power Limited

on version PS5-XX025-B03-CE

Caution

For continuous protection against

fire hazard, replace only with the

same type and rating of fuse