background image

I.

Model Numbers

18Ah

28.2VAC

2.50A

36Ah

2.5A

24VDC

PS5-24025-B07-UL/CSA/ULC

 01347

36Ah

17.5VAC

1.25A

36Ah

2.5A

12VDC

PS5-12025-B07-UL/CSA/ULC

 01339

Max.

Battery

Storage

XFMR

Voltage

Max. AC

Input

Current

Max.

Battery

Capacity

System
Current

System
Voltage

Model Number

AS

Order

No.

       UL1481 - Power Supply/Battery Charger, Guide UTRZ

Power Supply/Battery Charger for use with Listed devices shown in Addendum "A".

       UL294 - Access Control Systems Unit Accessory, Guide ALVY

Power Supply/Battery Charger for Access Control Applications

       ULC-S527 - Fire Alarm Power Supply/Battery Charger
       CSA C22.2 No. 107.1 - Commercial and Industrial Power Supply
* UL Listed Products comply with NFPA 72 - National Fire Alarm Code.

II.

Installation Instructions

1. Mount cabinet per mechanical dimensions and knockout locations given in Section IV.
2. Connect 120VAC, 60Hz., single phase to the black and white leads of the transformer in  accordance

with Article 725 or Article 760 of the National Electrical Code or Article 16 or 32 of the Canadian
Electrical Code. 

3. Low Volt AC Input - Connected to secondary winding of the transformer.

v

 Fused at 10 Amps (Fuse Type AGC-10)

4. Verify output voltage at "DC Output" and "Battery" terminals.

12V system measures approximately 13.8VDC.
24V system measures approximately 27.6VDC.

5. Connect battery set to "Battery" terminals.

CAUTION: Observe polarity; incorrect polarity will destroy battery fuse.
Fused at 10 Amps (Fuse Type AGC-10).
Recommended battery type - PowerSonic (PSSeries) or YUASA (NPSeries) sealed lead acid/gel cell.
The Battery terminals are Nonpower limited. Wiring of the batteries must conform to the Power Limited
Wiring Requirements in Section V, and to Article 760 of the National Electrical Code or Article 16 of the
Canadian Electrical Code.

6. Connect "DC Output" to input of user system.

CAUTION: Observe polarity; incorrect polarity may damage user system.
Refer to Section I for Maximum Allowable System Current.
Output terminals are POWER LIMITED

7. Visual Indicators:

AC Presence LED1:

Green LED

System OK     LED3:

Green LED

LED2 (Red LED) serves no user function.

8. Connect "Fault Output" to system fault annunciation.

Form "C" Relay Contacts rated 1 Amp @ 24VDC resistive
Relay Contacts labeled in the non-operational (fault) condition.
Fail-safe; active until an actual fault condition.

9. Fault Conditions:

Low AC / No AC / Blown AC Fuse / Low Battery / Blown Battery Fuse

CAUTION: Fault condition reporting may be delayed dependent on power supply loading.
The battery set is NOT supervised for presence.

10. Battery Standby Information:

a) For 60 hr. standby with 36Ah battery set - Max standby draw: .5A, Max 5 minute alarm current: 2A.

b) For 24 hr. standby with 36Ah battery set - Max standby draw: 1A, Max 5 minute alarm current: 2A.
c) For 4 hr. standby with 20Ah battery set - Max standby draw: 2.5A, Max 5 minute alarm current: 2.5A.

11. Power Supply System Draw (No AC, No load) is 25mA.

III.

Typical Hook-up Diagrams

            Power Supply/Battery Chargers

                      Installation Instructions

AlarmSaf

 

w

 

65A Industrial Way 

w

 Wilmington, MA USA 01887-3499 

w

 (978) 658-6717 

w

 FAX: (978) 658-8638  Web Site:  www.alarmsaf.com

52-133X
090897

AC FUSE  (AGC-10)

BATT FUSE  (AGC-10)

LOW

VOLT

AC

CONNECT

BATTERY

CONNECT

+

_

DC

OUTPUT

+

_

NC

C

NO

FAULT

OUTPUT

PS5-XX025 

Input and Output Terminals

Low Volt AC Input Terminals

and Battery Terminals are

Nonpower-Limited

DC Output Terminals and Fault

Output Terminals are

 Power Limited

Caution

For continuous protection against

fire hazard, replace only with the

same type and rating of fuse