Integrated control
3313737
7.2
HMI Room quick start guide
ART Tech Level II
Quick Guide to HMI Room (Room Control Panel)
Display range
Temperature setpoint
Time (error code when an alarm is pending)
Fan steps:
1-stage plants:
Off = no display
On = 6 bars
2-stage plants:
Off = no display
Stage 1 = 3 bars
Stage 2 = 6 bars
3-stage plants:
Off = no display
Stage 1 = 2 bars
Stage 2 = 4 bars
Stage 3 = 6 bars
Automatic: Fan steps are selected automatically
Weekday: 1 = Monday, 2 = Tuesday, 3 = Wednesday, …
Plant OFF
Automatic: Plant switched by time program or building man-
agement system
Plant ON in economy mode (reduced temperature setpoint)
Plant ON in comfort mode
Cooling ON
Heating ON
Plant ON: Party mode
Alarm
Heat recovery ON
FAN button
OK button
PLUS button
MINUS button
PROG button
PARTY button
MODE button
ON/OFF button
Switching the plant (only with switching authorisation)
If is displayed at the top left, the plant is off. Press
ON/OFF
to switch the plant
on.
The plant operating mode can then be switched (see
Switching the operating
mode
).
Setting the time/date
Use
PROG
to switch to the time and date setting.
Press
PLUS
or
MINUS
to set the individual numbers and confirm with
OK
.
Party mode
1. Press
PARTY
to start the party mode.
The symbol is displayed and, instead of the time, the remaining run time of
P1:00
(= 1 hour and 59 minutes) is displayed.
Press
PARTY
again to prematurely end the party mode.
2. Press
PLUS
to increase the remaining run time by 1 hour.
Press
MINUS
to decrease the remaining run time by 1 hour.
3. Press
FAN
to switch in a cycle between:
Stage 1, Stage 2, Stage 3
and Automatic .
Setting the temperature setpoint (not possible in party mode)
Press
PLUS
or
MINUS
to increase or decrease the setpoint by 0.5 °C.
Important information!
1. The switching authorisation of the room control panel depends on the setting
in the controller (see operating manual).
2. The possible setting range of the temperature setpoint depends on the setting
in the control (see operating manual).
3. Flashing symbols in the display area indicate that the room control panel has
been overridden by the controller.
4. The number of TSP steps and the availability of the economy mode depend on
the configuration of the plant (see operating manual).
5. In economy mode, the plant is operated at a reduced temperature setpoint. See
the operating manual for further information.
Alarm display and acknowledgement
1. If is displayed, an alarm is pending. Most alarms display an error code in
addition to the symbol. This appears on the display instead of the time (e.g.
A:81). See the operating manual for a description of the error codes.
2. Keep
OK
pressed for one second to start an acknowledgement attempt.
Setting the fan steps (only with switching authorisation)
Press
FAN
to switch in a cycle between:
Stage 1, Stage 2, Stage 3
and Automatic .
Switching the operating mode (only with switching authorisation)
1. Make sure that the plant is switched on (see
Switching the plant
).
2. Press
MODE
to switch in a cycle between:
Comfort , Economy and Automatic .
In Automatic, the time program or building management system decides on
the operating mode.
3421379
Содержание EASYAIR RO-01
Страница 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Страница 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Страница 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Страница 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Страница 74: ......
Страница 75: ......