![AL-KO AIRCABINET Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/al-ko/aircabinet/aircabinet_installation-and-operating-manual_2887690030.webp)
Translation of the original operating manual
30
AL-KO
AIR
CABINET
®
5.5.2 Overview
The combination exterior wall diffuser is used to produce a building passageway in a sandwich window element, for air
exchange via an
AL-KO
AIR
CABINET
®
compact air handling unit. The piping for outdoor air and exhaust air is connected
to the combination exterior wall diffuser.
1
2
2
3
3
4
4
7
12
6
13
5
8
1
9
10
11
10
11
5
4
6
7
1
Exhaust air outlet
8
Outdoor air breakthrough
2
Exhaust air fitting
9
Exhaust air breakthrough
3
Combination exterior wall diffuser
10
Sandwich window element (customer provision)
4
Outdoor air intake
11
Sealing compound for window sandwich element
5
Inside cover
12
Sealing compound for combination exterior wall diffuser
6
Screw connection holes
13
Rear wall
7
Outdoor air fitting
5.5.3 Creating and inserting a sandwich window element
A sandwich window element (10) is to be installed on site instead of a window pane in a window element by a glazier. It
must have sufficient stability to ensure the firm, torsion-free fit of the combination exterior wall diffuser (3). It must be
manufactured to fit exactly; use the inside cover (5) as a template for this purpose.
Apply an approximately 15 mm thick sealing compound strip (12) to the edge of the sandwich window element (10)
before pressing and screwing into the window replacement element.