Translation of the original operating manual
20
AL-KO
AIR
CABINET
®
3.1.14 Piping
L
R
1
1
5
5
2
3
3
2
4
4
L
Air distributor module, outside air / exhaust air fitting, left
side
3
Supply air fitting
R
Air distributor module, outside air / exhaust air fitting,
right side
4
Exhaust air grille
1
Exhaust air fitting
5
Silencer module
2
Outdoor air fitting
The air distributor module of the compact air handling unit is available in two versions: Depending on the requirements of
the spatial conditions, either with the two ø 250 mm round pipe fittings of the connections for outdoor air (2) and outgo
-
ing exhaust air (1) on the left side (L) or on the right side (R). This depends on the direction in which the outdoor air and
outgoing exhaust air piping to a window replacement element or another external wall passage can optimally take place.
The piping can be implemented using permanent piping which is installed and insulated on site, using fittings or using
flexible, insulated hoses which are available from AL-KO THERM GmbH.
The ø 280 mm round pipe fitting for the supply air (3) can be optionally piped; however, piping is not mandatory. This can
be carried out either using a textile air hose fitted on site and available as an option from AL-KO THERM GmbH or using
an air line with air passages. The supply air can also exit directly from the fitting into the interior space.
The exhaust air (4) is extracted directly on the unit, no piping is provided.
3.1.15 Technical data
Data
AL-KO
AIR
CABINET
®
Dimensions (W x D x H) in mm
1305 x 730 x 2477
Overall weight in kg
406
Air distributor module (W / D / H) in mm
1305 x 730 x 321
Air distributor module weight in kg
35
Silencer module (W / D / H) in mm
1305 x 730 x 983
Silencer module weight in kg
158
Basic unit (W / D / H) in mm
1305 x 730 x 1173
Basic unit weight in kg
213
Round pipe fitting connection for exhaust air, outside air
ø 250 mm
Round pipe fitting connection for supply air
ø 280 mm
Exhaust air filter - filter class / dp End [Pa]
ePM10-50 / 150
Outdoor air filter - filter class / dp End [Pa]
ePM1-75 / 290
Electric air heater, 3-stage
1.5 kW
Hygienic unit design
VDI Directive 6022
Air volumes
800 - 1600 m
3
/h
Unit mains connection
230 V / 16 A
Article no., air distributor module with outside air / exhaust air fitting, left
3420860
Article no., air distributor module with outside air / exhaust air fitting, right
3420861