Appendix B Configuration parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
33
33
Appendix B Configuration parameters
Table B.1
No
Name
Parameter
Valid value
Meaning
Config-
urator
Display
PL-0 / Basic parameters
1
dev
Device
read only
2
ver
Firmware
read only
3
n.Err
Last error code
read only
4
ind.t
Channel display duration at
cyclic indication (s)
1…600
5
ind.r
Display update (s)
0…60
6
ind.A
Cyclic indication after
restart
ON
OFF
7
AL.dr
Alarm output
0…8
8
ALHd
Alarm duration (s)
1…600
9
AL.St
Alarm output state
ON
OFF
10
Cj-C
Cold junction compensation
(CJC)
ON
OFF
11
SYSt
System error indication
ON
OFF
12
bL.Ar
Manual mode lock
ON
OFF
PL-1 / Inputs
1
in.Fd
Filter time constant (s)
0…15
2
in.FG
Filter pass band
0…100*
3
Prt
Priority
1…8
4
in.SH
Offset
-
999…9999*
5
in.SL
Slope
0,900…1,100
6
Ain.L
Signal lower limit
-
999…9999*
7
Ain.H
Signal upper limit
-
999…9999*
8
in.rd
Differential filter time
constant (s)
0…15
9
in-t
Sensor type
OFF
RTD Cu100 (GOST)
RTD Cu50 (GOST)
RTD Pt100
RTD 100P (GOST)
TC type L (GOST)
TC type K
-
50…+50mV
RTD Pt50
RTD 50P (GOST)
RTD 50M (GOST)