Installation instructions

GB

D163H232 Ed.06

AKO-D16323

3

5

D

1

6

3

2

3

2 R

EV

.0

5 2

0

1

6

AKO ELECTROMECÀNICA, S.A.L.

We  reserve  the  right  to  supply  materials  which  may  be  slightly 
different  from  those  described  in  our  Data  Sheets.  Updated 
information on our web site:  

www.ako.com 

Av. Roquetes, 30-38
08812 Sant Pere de Ribes
Barcelona (España)

www.ako.com
[email protected]

Tel. (34) 938 142 700
Fax (34) 938 934 054

1- Warnings

-Using the equipment without following the manufacturer's instructions 

may affect the device's safety requirements. To ensure that the device 
operates correctly, only probes supplied by AKO should be used. 

-The unit must be installed in a location protected from vibrations, water 

and corrosive gases, where the ambient temperature does not exceed 
that shown in the technical data.

-To ensure a correct reading, the probe must be situated in a location 

without any external heat influences except for the temperature which 
is being measured or controlled.

-The power supply circuit must be provided with a main switch rated at at 

least 2 A, 230 V, located close to the equipment. The cables will enter 
through the back and should be type H05VV-F or H05V-K. 

-The gauge will depend on local regulations, but should in no case be less 

2

than 1 mm .

2

-Connecting wires for the relay contacts should be sized 2.5 mm .
-Between -40 ºC and +20 ºC, if the probe NTC is prolonged till 1.000 m with a 

2

mínimum  of  cable  0,5  mm ,  the  maximum  deviation  will  be  of  0,25  ºC 
(extension cable for probe ref. AKO-15586)

NOTE:

 Equipment not compatible with AKO-14917 (external communication 

module) and AKO-14918 (programming key)

2- Installation

3- Wiring

The probe and its cable should 

NEVER 

be installed in the same conduit 

as power, control or supply cables.

4- Operation

COOL relay ON

FAN relay ON

DEF relay ON

Alarm ON

Temperature

indication

Terminal blocks

UP (

N

) /SET key

DOWN (

Q

) key

UP

(

N

) /

SET

 key

Pressing  for  5  seconds  activates  Standby  mode,  pressing  for  2 
seconds returns the equipment to normal mode. In Standby mode, 
the equipment performs no actions and only the 

AKO

 indicator is 

displayed on the screen.
Pressing for 10 seconds goes to the programming menu.
In the programming menu, pressing for 5 seconds goes to the level 
displayed or, during the setting of a parameter, accepts the new value.
In programming menu, pressing briefly allows you to scroll through the 
various levels or, during the setting of a parameter, to change the value.

DOWN (

Q

)

 key

In programming menu, pressing briefly allows you to scroll through the 
various levels or, during the setting of a parameter, to change the value.

5- Start-up

On  power-up,  the  equipment  will  start  in  Wizard  mode  (InI  /  1 
flashing),  select  the  most  appropriate  application  using  the 

UP

  / 

DOWN

 keys and press 

SET

.

1

Multipurpose

2

Frozen

3

Fruits and vegetables

4

Fresh fish

5

Soft Drinks

6

Bottle racks

7

AC

The wizard will configure the parameters of the equipment for the 
chosen application (see table "Default settings by application").

124 mm

85 mm

1

A

1

A

A

S1

S2

DI1

DI2

1

8

2

9

3

10

4

11

5

12

6

13

7

AKO-D16323

COOL

CRANKCASE HEATER

FAN

I max.:

16 A
L N

9

0

-2

4

V

~

5

0

/6

0 H

z

5 sec.

Temperature

Indication

Release

SET

 to go to

Stand-by

Release 

SET

to access

programming

10 sec.

t

Change

Menu

Change

Parameters

Level 1

Menus

Temperature

indication

Level 2

Parameters

Level 3

Values

OK

Press

UP/
SET

>10 sec

.

Press

UP/
SET

<5 sec

.

Press

UP/
SET

<5 sec

.

Press

UP/
SET

<5 sec

.

Press

UP/
SET

>5 sec

.

Press

UP/
SET

<5 sec

.

Press

UP/
SET

<5 sec

.

Press

UP/
SET

repeatedly

Press

UP/
SET

repeatedly

Press

UP/
SET

<5 sec

.

Press

UP/
SET

<5 sec

.

OK

20 sec

20 sec

20 sec

OK

OK

OUT OF

PROGRAMMING

PROGRAMMING

Change

value

OK

Keep

UP / SET

pressed

Programming Menu (parameters)

Access to set point and Stand-by

After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved.

AUX.

AUX

AUX.

AUX

Operation as per 

parameter P6

S1: 

Probe 1, temperature in the chamber or cabinet.

S2: 

 Probe 2, defrost.

DI1/DI2:

 Digital Input 1 / Digital Input 2

User Manual available at