Pump down function

This function foresees problems in the compressor caused by movements of coolant, using a stop/start technique for 
the installation, controlled via the liquid solenoid, the low pressure switch and the compressor itself.
This function is only available for InI 2, 5 and 7 and requires the connection of a low pressure switch in digital input 
1 (I10=7).

STOP

When the temperature in sensor S1 reaches the set point (SP) value, the COOL relay deactivates, closing the solenoid 
valve.
Because the compressor continues to operate, pressure in the evaporator quickly drops. Upon reaching a given value, 
the low pressure switch activates, changing the status of digital input 1, which stops the compressor (AUX 1 relay).
This manoeuvre isolates all of the coolant in the high-pressure line, far from the compressor crankcase, preventing 
serious faults upon start-up.
Should the low pressure switch fail, the controller stops the compressor once the safety interval defined in C20 has 
elapsed, displaying the message “Pd” (an informative message that does not affect the unit's operation).
If C20 time is 0 (default value), the compressor will not stop until the low pressure switch is activated, but it will 
display the “Pd” message after 15 minutes.

START

When the temperature in sensor S1 reaches the set point value plus the differential (SP+C1), the COOL relay acti-
vates, opening the liquid solenoid. This increases the pressure in the evaporator, deactivating the low pressure switch, 
which turns the compressor on.
If, some time (determined by C19) after the liquid solenoid is opened (COOL relay set to ON), the low pressure 
switch does not deactivate, the controller will once again close the solenoid (COOL relay set to OFF) and the “LP” 
message will be displayed. This manoeuvre will be repeated every 2 minutes, indefinitely, until the pressure switch is 
deactivated and the installation reverts to its normal operation.
If C19 time is 0 (default value), the solenoid will remain open until the low pressure switch deactivates, but it will 
display the “LP” message after 5 minutes.

STAND-BY

If the pump down function is active, there may be a delay between starting the Stand-by function and the 
controller stopping; this is because certain installation control phases cannot be interrupted.
To force the stop of the controller, press the Stand-by key again for 3 seconds.

Liquid 
solenoid

Low pressure
switch

Pressure

switch fault

Pressure

switch fault

Compressor

Pressure in
evaporator

Содержание AKO-16526

Страница 1: ...351652602 Ed 03 EN AKO 16526 Temperature and electronic expansion controller for cold room store User manual...

Страница 2: ...mec nica accepts no liability for damage which may occur due to failure to comply with these regulations Rigorously follow the instructions described in this manual In order to extend the lifetime of...

Страница 3: ...e used in a place without heat influences apart from the tem perature you want to measure or control The IP65 protection degree is only valid with the protection cover closed The IP65 protection degre...

Страница 4: ...LIQUID SOLENOID THERMOSTATIC EXPANSION VALVE EVAPORATOR CONDENSER S1 FAN COOL D1 AUX 1 S2 PAR METROS Tipo de v lvula u00 Solenoide 0 Sondas conectadas I00 Temp c mara temp Evap 2 Configuraci n D1 S3...

Страница 5: ...sonda S6 I61 1 2 3 o 4 Rel AUX 1 o00 Compresor Res c rter 1 LIQUID CONTAINER COMPRESSOR FREQUENCY CONVERTER CONDENSER EVAPORATOR S1 S2 S5 S6 FAN AN OUT COOL D1 AUX 1 ON OFF Reg 4 20 mA 0 10 V PWM VAL...

Страница 6: ...something is preventing them from activating Pulsing evaporator fans controlled by analogue output Constant the COOL relay is active Flashing the COOL relay should be active but a delay or protection...

Страница 7: ...deactivates the cold room light Pressing it for 3 seconds accesses the condensed programming menu Pressing it for 6 seconds accesses the expanded programming menu In the programming menu it accesses t...

Страница 8: ...box Mark and make the holes in the wall with the aid of the template included Fix the device to the wall If it is a brick wall use the screws and plugs supplied if the wall is made of sheet metal col...

Страница 9: ...for relay or contactor outputs should have a section of 2 5mm2 allow working temperatures equal to or over 70 C and be installed with as little bending as possible The 120 230 V wiring area must be ke...

Страница 10: ...the fan control is ON OFF F10 0 or an external frequency inverter is used for ventilation F10 1 The second option is only available if a STEPPER type electronic expansion valve u00 2 is not used Anal...

Страница 11: ...0 0 0 0 20 0 0 2 Yes Yes Electric Yes 1 1 2 7 1 0 0 20 0 0 3 Yes No Electric Yes 0 1 2 0 0 0 0 20 0 0 4 No No Air Yes 0 0 1 0 0 0 0 20 1 1 5 Yes Yes Air Yes 1 1 1 7 1 0 0 20 1 1 6 Yes No Air Yes 0 1...

Страница 12: ...u02 4 R410A u02 5 R450A u02 6 R513A u02 7 R744 u02 8 R449A u02 9 R290 u02 10 R32 u02 11 R448A u02 12 R1234ze u02 13 R23 u02 14 R717 u02 15 R407C u02 16 R1234yf u02 17 R22 u02 18 R454C u02 19 R455A u0...

Страница 13: ...controller stops See page 17 Operation Messages 10 SET 11 SET 12 SET Pump down malfunction error Stop The time configured in parameter C20 has been exceeded See page 17 Only displayed on screen Pump d...

Страница 14: ...d the audible alarm Minimum superheat alarm The value set in A20 has been reached See page 25 Acti vates the alarm relay and the audible alarm Minimum superheat alert The value defined in A23 has been...

Страница 15: ...pressure in the evaporator to increase and therefore the low pressure switch deactivates and the compressor starts up Once the set point SP value is reached the solenoid closes causing the pressure in...

Страница 16: ...line of the display by default Parameter b23 defines which value is displayed on that line When there is no cooling required the superheat value is not updated as the regulation is stopped When the c...

Страница 17: ...ressor will not stop until the low pressure switch is activated but it will display the Pd message after 15 minutes START When the temperature in sensor S1 reaches the set point value plus the differe...

Страница 18: ...oned value may be negative or positive which allows for the Set Point to be reduced or increased If it is configured in 0 the mode is disabled It is activated in three possible ways By means of an ext...

Страница 19: ...e controlled should the cold room door open through parameters C22 and C23 Parameter C22 defines whether cold production should be stopped if the door opens If C22 1 when the door opens the fans stop...

Страница 20: ...m change parameter F3 to 0 The compressor and solenoid are stopped Hot gas InI 7 and 8 d7 2 The hot gas from compressor discharge is used to melt evaporator ice and to this end two valves are necessar...

Страница 21: ...start up delay This is established through parameter F4 and allows for the possible drops left in the evaporator to freeze before the fans activate preventing them from being projected into the cold r...

Страница 22: ...porator defrost o10 4 Defrost begins simultaneously in both evaporators When the sensor of evaporator 1 reaches the temperature defined in d4 the DEF relay deactivates completing defrost of evaporator...

Страница 23: ...C22 defines whether fans stop when the door is opened ON OFF control F10 0 This type of control starts or stops the fans depending on the temperature at sensor S2 If F2 0 the fans start when the tempe...

Страница 24: ...and will deactivate when 10 degrees are reached If A0 1 absolute the maximum temperature alarm will activate when 10 degrees are reached in sensor 1 and will deactivate when 8 degrees are reached Exte...

Страница 25: ...door alarm is activated In order to detect the open door configuration is required of one of the digital inputs as door contact l10 l20 or l30 1 Activates alarm relay and audible alarm Minimum superhe...

Страница 26: ...OFF without alarm A9 1 Relay inactive OFF in the event of an alarm ON without alarm Alerts The device alerts the user through an on screen message when an event occurs which requires his her attention...

Страница 27: ...and deactivated by means of AKONet software AUX 2 relay Deactivated o10 0 does not carry out any function Alarm o10 1 this activates the relay every time that an alarm occurs See page 24 Light o10 2...

Страница 28: ...defrost duration 0 defrost deactivated min 0 255 d4 Final defrost temperature by sensor If I00 1 C F 50 8 0 50 SH Superheating set point K 0 1 8 40 F3 Status of the fans during the defrost 0 stopped 1...

Страница 29: ...enter the password programmed in PAS when attempting to access either of the two functions If the entered password is not correct the unit will go back to showing the temperature IMPORTANT certain pa...

Страница 30: ...e of relay ON if sensor 1 damaged if C7 0 and C8 0 the relay will always be OFF when disconnected min 0 10 120 C8 Time of relay OFF if sensor 1 damaged if C8 0 and C7 0 the relay will always be ON whe...

Страница 31: ...d6 0 0 1 d6 Delay of the defrost start on connecting the unit min 0 0 255 d7 Type of defrost 0 resistors 1 air fans 2 hot gas 0 2 d8 Time calculation between defrost periods 0 total real time 1 sum o...

Страница 32: ...lue D 0 0 100 u07 Opening value of the electronic expansion valve when cooling is activated u13 50 u12 u08 Duration of valve opening on cooling demand s 2 5 240 u09 Valve opening value with sensor err...

Страница 33: ...F without alarm 1 relay OFF in alarm ON without alarm 0 0 1 A10 Differential of temperature alarms A1 and A2 C F 0 1 1 0 20 0 A12 Delay of open door alarm if I10 I20 or I30 1 min 0 10 120 A20 Minimum...

Страница 34: ...ation 0 deactivated 1 door contact 2 external alarm 3 severe external alarm 4 change SP 5 remote defrost 6 defrost lockout 7 low pressure switch 8 remote activation in Stand by mode 9 product temperat...

Страница 35: ...noid status 7 equal device status 0 2 7 o20 AUX 3 relay configuration 0 deactivated 1 alarm 2 light 3 external AO controller ON OFF 4 defrost 2nd evaporator 5 resistor door frame 0 0 5 o30 Analogue ou...

Страница 36: ...m 0 Terminating resistors are not required SECURE CONTROL Connectivity The controllers are equipped with a port for connection of RS485 MODBUS data which allows for remote manage ment of these using...

Страница 37: ...y 1 C Tolerance of the NTC probe at 25 C 0 4 C Input for NTC probe AKO 14901 Working ambient temperature 10 C to 50 C Ambient storage temperature 30 C to 60 C Protection degree IP 65 Installation cate...

Страница 38: ...351652602 Ed 03 38...

Страница 39: ...351652602 Ed 03 39...

Страница 40: ...vda Roquetes 30 38 08812 Sant Pere de Ribes Barcelona Spain www ako com We reserve the right to supply materials slightly different to those described in our data sheets Updated information on our web...

Отзывы: