PID controller's size 48 x 48 mm

Controller designed to display and control the process, with tight adjustment PID control, in appliances 
where accuracy is required, like water or oil cooling systems, furnaces, gas burners, plastic injection 
machinery, etc. 
Input for type 4-20 mA, Pt100 sensors, Thermocouple J or Thermocouple K. Relay outputs may be used for 
control and/or alarm. It also has a logic output/input for control/alarm.

1- Versions and references

2- Installation

The controller should be installed in a place protected from vibrations, water and corrosive gases, and 
where ambient temperature does not surpass the value specified in the technical data.
In order for the controllers to have IP55 protection, the gasket should be properly installed between the 
apparatus and the perimeter of the panel cut-out where it is to be fitted.
In order to give a correct reading, the probe should be installed in a place without heat influences other 
than the temperature that is to be measured or controlled.

2.1-Fastening

To fix the unit, place the fasteners in the top and the 
lower parts and press them to enter in the controller 
lateral sliders. Move the fasteners in direction to the 
panel until the controller is fixed.

2.2- Connection

The probe and its lead should 

NEVER

 be installed in 

ducting along with power, control or power supply 
wiring.
The power supply circuit should be connected with a 
minimum 2 A, 230 V, switch located close to the unit. 

2

Power supply cables should be H05VV-F 2x0,5 mm  

2

or H05V-K 2x0,5 mm .Section of connecting wires for 

2

2

relays contacts should range from 1 mm  to 2,5 mm . 
For  the  4-20  mA  control  input,  it  is  necessary  to 
connect  the  2.49 

W

  resistance  supplied  between 

terminals 10 and 11.

3- Adjustment and configuration

It should only be programmed or modified by personnel 
who are fully conversant with the equipment operation 
and possibilities.

3.1 Set Point temperature.

The factory SET POINT default value is 0,0 ºC.
-Press 

PRG 

key for at least 3 seconds to CHANGE SET POINT SP1 or SP2. It displays SP1.

-Press 

N

 or 

Q

 keys to SELECT SET POINT 1 or 2.

-Press 

SET 

key to CHANGE SELECTED SET POINT. It displays the CURRENT SET POINT value.

-Press 

N

 or 

Q

 keys to CHANGE SET POINT into the required value.

-Press 

SET 

key to ACCEPT THE NEW SET POINT. The display returns to the CURRENT TEMPERATURE 

display status.

3.2 Parameters configuration

Level 1 Menus

-Press 

PRG 

key  for  at 

least 10 seconds. We are 
in the programming LE-

VEL  1  MENUS  and  the 

first menu “

SPCF

” is dis-

played.

-Press 

N

 

key to access the next menu and 

Q

 

key to return to the previous one.

-Press 

PRG 

key, the controller returns to the CURRENT TEMPERATURE display status.

When 

PAS

 is displayed, PASSWORD programmed in 

PAS1

 parameter of 

PAr

 menu should be entered

to access programming LEVEL 1 MENUS.
-Press 

N

 or 

Q

 keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.

-Press 

SET 

key to ACCEPT PASSWORD. The first menu “

SPCF

” will be displayed.

Level 2 Parameters

-In the desired menu of LEVEL 1 MENUS, press key 

SET

. LEVEL 2 PARAMETERS programming is accessed. 

The first parameter of the selected menu is displayed on the screen.

-Press 

N

 key to access the next parameter and 

Q

 

key to return to the previous one.

-Pressing 

PRG 

key, returns to the LEVEL 1 MENUS.

Level 3 Values

-Press  the 

SET

  key  to  enter 

and modify the desired para-

meter.

-Press 

N

  or 

Q

  keys  to 

CHANGE VALUE.

-Pressing 

SET

  key,  ACCEPT 

THE  NEW  VALUE  and  it 
returns  to  LEVEL  2  PARA-

METERS.

-Pressing 

PRG

 key, it returns 

at  LEVEL  2  PARAMETERS 
without modify value.

REMARK:

 If no key is pres-

sed for 25 seconds in either of 

the  previous  steps,  the 
controller  will  automatically 
return  to  the  CURRENT 
TEMPERATURE display status 
without modifying any of the 
parameters values.

4- Operation

PRG key: 

Accepts the alarms and disconnects alarm outputs. When pressed for at least 3 seconds, the SP 

SET POINT temperature value is displayed. When pressed for 10 seconds display the first level of menu 
SPCF of parameters. Exit programming level.

Key 

Q

:

 

Accepts the alarms and disconnects alarm outputs. In 

programming, it makes the displayed value reduce.

Key 

N

:

 

Accepts the alarms and disconnects alarm outputs. In 

programming, it makes the displayed value increase.

SET  Key: 

Accepts  the  alarms  and  disconnects  alarm  outputs. 

When pressed during 3 seconds, it activates the Autotune function 
if AtEn=1. Deactivates the Autotune function. In programming, 
accept the programmed new value.

LED OUT1:

 CONTROL 1 indicator activated.

LED AL1:

 Alarm 1 indicator enabled. Flashing: Alarm 1 detected, relay deactivated but signalling 

maintained.

LED OUT2/AL2:

 CONTROL 2 or Alarm 2 indicator enabled. Flashing with Alarm 2: Alarm 2 detected, 

relay deactivated but signalling maintained.

LED AT:

 Autotune indicator enabled.

4.1 Control 1, control 2 and alarms operation

AUTOTUNE:

 Press 

SET

 key for 3 seconds to activate a SELF-ADJUSTMENT (AUTOTUNE). The controller 

will configure automatically the parameters at process characteristics setting.

Gain (GAin):

 The output it is configured proportional to the error signal width.

Overall time (ti):

 The final error it is eliminated by the output regulation proportionally to the error signal 

width and duration.

Derivative time (td):

 It determines the controller reaction on process temperature changing. Over and 

lower pulses prevention. It is also used to quick actuation on the variable process value in the event of a 
sudden change in the set point.

CURRENT

TEMPERATURE

D

IS

PL

AY

SE

PO

IN

SP

A

C

C

EP

T

TH

N

EW

CURRENT

SET POINT

NEW

SET POINT

3 SeC.

C

H

A

N

G

E

SE

PO

IN

T

SE

LE

CT

SE

PO

IN

T

or 

2

CURRENT

TEMPERATURE

PASSWORD

IF PROGRAMMED

LEVEL 1

MENUS

LEVEL 2

PARAMETERS

LEVEL 3

VALUES

10 Sec.

IF PAS1=0

PASSWORD

REQUEST

C

H

A

N

G

E

N

U

M

BE

R

DISPLAY

PASSWORD

A

C

C

EP

T

PA

SS

W

O

RD

D

IS

PL

AY

PA

RA

M

ET

ER

C

H

A

N

G

E

VA

LU

E

A

C

C

EP

T

TH

N

EW

EXIT

PROGRAMMING

EXIT TO

LEVEL 1

AKO-15400
AKO-15401
AKO-15402
AKO-15403
AKO-15410
AKO-15413
AKO-15415
AKO-15430
AKO-15437
AKO-15450
AKO-15451
AKO-15452
AKO-15453
AKO-15460
AKO-15463
AKO-15465
AKO-15480
AKO-15487

No

Yes

No

Yes

No
No

Yes

No
No
No

Yes

No

Yes

No
No

Yes

No
No

No
No
No
No
No

Yes

No

Yes
Yes

No
No
No
No
No

Yes

No

Yes
Yes

No
No

Yes
Yes

No
No
No
No

Yes

No
No

Yes
Yes

No
No
No
No

Yes

No
No
No
No

Yes
Yes
Yes

No
No
No
No
No
No

Yes
Yes
Yes

No
No

20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC
20 to 48 V AC/DC

100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz
100 to 240 VAC 50/60Hz

Model

CT Module 4-20mA/0-10V

Module

RS485

Module

Relay 3

Module

Supply

PANEL

CUT-OUT

45 mm

45 mm

105 mm

max. 13 mm

CT MODULE
CURRENT
TRANSFORMER

4-20 mA 0-10 V

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

TOP

DIGITAL

INPUT

SSR

OUTPUT

+

L

N

R1

R2

Pt100

RS485
COMMUNICATION
MODULE

R3 RELAY
MODULE

OUTPUT
MODULE
4-20 mA / 0-10 V

~

+

+

GND B

A

+

TC

+

4-20 mA

GND

R<220

W

 

R

R=2.49  

W

EXIT TO

LEVEL 2

OFF

ON

diF1 > 0

diF1 > 0

OFF

ON

diF1 < 0

diF1 < 0

C1

C1

VALUE

VALUE

VALUE

VALUE

SP2 + diF2

Stop

SP2

Start

diF2 > 0

diF2 > 0

C2

SP2

Stop

VALUE

VALUE

VALUE

VALUE

C2

diF2 < 0

diF2 < 0

SP2 - diF2

Start

DIRECT operation

REVERSE operation

o2C=0 Two independent stages and ON/OFF control type

HC1 = 1 for CONTROL 1

HC2 = 1 

 CONTROL 2

for

HC1 = 0 

 CONTROL 1

for

HC2 = 0 

 CONTROL 2

for

SP1

Start

SP1 + diF1

Stop

SP1 - diF1

Start

SP1

Stop

SP2 + diF2

Start

SP2

Stop

SP2

Start

SP2 - diF2

Stop

SP1

Stop

SP1 + diF1

Start

SP1 - diF1

Stop

SP1

Start

SP1-SP2-diF1

Start

OFF

ON

OFF

ON

REVERSE operation

HC1=1  diF1<0   SP2<0

C2

SP1-SP2

Stop

SP1

Stop

SP1 - diF1

Start

C1

SP1 + diF1

Start

SP1

Stop

C1

DIRECT operation

o2C=1 Two related stages

HC1=0  diF1>0  SP2>0

VALUE

VALUE

SP1+SP2+diF1

Start

SP1+SP2

Stop

C2

OFF

ON

OFF

ON

VALUE

VALUE

SP1

Stop

SP1 - diF1

Start

C1

SP1 + diF1

Start

SP1

Stop

C2

o2C=2 Neutral Zone

LED

AL1

Key

Key

Key

Key

PRG

SET

Down

Up

LED

 OUT1

LED

OUT2/

AL2

LED

AT

C1

C1

C2

C2

Отзывы: