AKO Electronica AKO-14722 Скачать руководство пользователя страница 1

LED ºC

LED ºF

LED R2

PRG

SET

UP
key

DOWN
key

ºC

ºF

1
2

3
4

LED R1

LED ºC

LED

R1

UP
key

DOWN
key

ºC

ºF

LED

R2

SET
key

LED ºF

1

2

3

4

Rail DIN

Panel mounting

www.ako.com

HOJA TÉCNICA

1472H206

Edición 01

(01 de 02)

Configurable electronic thermostats
with 2 relays and up to 2 probes

GB

Examples of some of the many applications

5 - CONFIGURATION AND ADJUSTMENT

CONFIGURATION:

It should only be programmed or modified by personnel who are fully con-

versant with the operation and possibilities of the equipment.

Level 1

Parameters

- Press the CONFIGURE OR ADJUST keys for 10 seconds. The LED “

ºC

” will be flashing to

indicate programming phase and the first parameter “

01

” will appear on the display.

- Pressing the   (   key accesses the next parameter and the   (   key will produce a return to

the previous one.

- Pressing DISPLAY VALUE key in the last display EP the controller will return to the current

temperature display status and the LED “

ºC

” will stop flashing.

Level 2

Values

- In order to display the current value of any parameter, select the desired parameter and

press the DISPLAY VALUE keys. Once it is displayed, it can be modified by pressing the

(   or   (   keys

- Pressing the ACCEPT THE NEW keys sets the new value. When this operation is performed,

the programming returns to Level 1 (parameters).

The two probe inputs can be inte-
rrelated with the two relay outputs
for the thermometer, thermostat
and the timing functions in cold and
heat applications.

CONFIGURATION

allows that

some parameters are 

ADJUSTA-

BLE

or not by the 

USER

so that he

or she has the exclusive informa-

Index:

1 - Versions and references

6 - Description of parameters and messages

2 - Technical data

7 - Relays R1 and R2 operation and control

3 - Installation

8 - Parameters transfer

4 - Front panel functions

9 - Maintenance

5 - Configuration and adjustment

10 - Warnings

1 - VERSIONS AND REFERENCES

MODEL

AKO-14722

AKO-14723

AKO-15223

FASTENING UNIT

Panel mounting

Panel mounting

DIN Rail

POWER SUPPLY, 50/60Hz

12V   ±20%

230V

~

±10%

230V

~

±10%

2 - TECHNICAL DATA

Temperature range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  (-58ºF a 211ºF) -50ºC a 99ºC

S1

input for NTC probe:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

AKO-149XX

S2

input for NTC probe:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

AKO-149XX

Controller accuracy:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  ±1ºC
Probe tolerance at 25ºC:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  ±0,4ºC
Relay 

R1

:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16(4)A*, 250V, cos

ϕ

=1, SPST

Relay 

R2

:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8A*, 250V, cos

ϕ

=1, SPDT

Maximum input power:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5VA
Working ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5ºC a 40ºC
Storage ambient temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC a 70ºC
Installation category: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II según norma CEI 664
3 digits and an optional decimal point when programmed
Double insulation between the power supply, the secondary circuit and the relay output.

* The current specified for each relay is its individual maximum. When more than one relay is
connected, the total current cannot surpass 17,5A (EN61010) or 13A (EN60730).

3 - INSTALLATION

The controller must be installed in a place protected from vibrations, water and corrosive gases,
and where the ambient temperature does not surpass the values specified in the technical data.
In order for the panel mounting units to be suitable having IP65 protection, the gasket should
be installed properly between the apparatus and the perimeter of the panel cut-out where it is
to be fitted.
In order to give a correct reading, the probe has to be installed in a place without heat influen-
ces other than the temperature that is to be measured or controlled.

3.2 Fastening units for DIN rail mounting:

4 - FRONT PANEL FUNCTIONS

4.1 Panel mounting models:

 PANEL CUT-OUT

28,5

70,5

3

2

1

max.

18 mm

61,5

44

90

35

58

45

To fix the unit, place the faste-
ners 

1

over the sliders 

2

as

shown in the figure. Move the
fasteners in the direction of the
arrow. By pressing tab 

3

the fas-

teners may be moved in the
opposite direction of the arrow.

4.2 DIN Rail models:

4.3 Common functions:

UP key

(factory default)

By pressing this key, the temperature in probe 2 is displayed.
By pressing it during 5 seconds, the R2 SET POINT is displayed.
In programming, it increases the value being displayed.

UP key

(configurable)

By default, the configuration of this key is factory-set for the preceding actions. However,
it can be configured according to the options of parameters 42, 43.

DOWN key

(factory default)

By pressing this key during 5 seconds, the R1 SET POINT is displayed.
In programming, it decreases the value being displayed.

DOWN key

(configurable)

By default, the configuration of this key is factory-set for the preceding functions.
However, it can be configured according to the options of parameters 44, 45.
+    

UP + DOWN keys

(in panel mounting models)

SET key

(in DIN rail models)

Pressing these keys during 10 seconds accesses to the configuration of the contro-
ller parameters.

+    

UP + DOWN keys

(in panel mounting models)

SET key

(in DIN rail models)

Pressing these keys once accesses to the adjustment of the user’s parameters.
By default, the configuration of these keys is factory-set for the preceding function.
However, they can be configured according to the options of parameter 46.

LED ºC

Permanent:

Temperature display in ºC.

Flashing:

Parameters programming phase.

LED ºF

Permanent:

Temperature display in ºF.

LED R1 Permanent:

Relay R1 activated.

LED R2 Permanent:

Relay R2 activated

3.1 Fastening units for panel mounting:

EXIT

PROGRAMMING

CURRENT

TEMPERATURE

LEVEL 1

PARAMETERS

LEVEL 2
VALUES

10 Sec.

SIMULTANEOUSLY

SIMULTANEOUSLY

SIMULTANEOUSLY

DISPLA

Y

VA

L

U

E

CHANGE

VA

L

U

E

ACCEPT

THE NEW

CURRENT VALUE

NEW VALUE

ºC

ºF

SET

10 Sec.

CONFIGURE

OR ADJUST

Heat:
Thermostat with two probes to display and
control.
Thermostat with control relay and alarm relay.
Action thermostat by a temperature difference
between the two probes.
As two simple thermostats.
As two cyclic timing devices without enabling
the probes.

Cold:
Double controller with defrost by compressor
stop.
Simple controller with defrost by compressor
stop and alarm relay.
Simple controller with defrost by air.
Simple controller with defrost by electric heat.
Thermostat with two phases or with a neutral
zone.

3.3 Connection:

See diagram in the unit rating plate.
The probe and its lead shoud 

NEVER

be installed in ducting along with power, control or power

supply wiring.
The power supply circuit should be connected with a minimum 2A, 230V, switch located close
to the unit. The cables should be of the type H05VV-F 2x0,5mm

2

or H05V-K 1x0,5mm

2

.

Section of connecting wires for relays contacts must be between 1mm

2

and 2,5mm

2

tion and adjustment that the device’s use requires. The functions of the front part keys as well
as the display of temperatures can be modified, while the configuration with a password can
be blocked.

ADJUSTMENT:

Pressing once the CONFIGURE OR ADJUST keys accesses the user’s para-

meters adjustment. The proceeding is the same as for the configuration and access is only
possible to the parameters defined as adjustable by the user in the configuration. In order to
access the parameters the parameter 39 parameter should be configured.

REMARK:

If no key is pressed for 25 seconds in any of the previous steps, the controller will

automatically return to the current temperature display status without modifying any of the
parameters values.

Отзывы: