Error 1: Thermostat (wireless) - Main control board
This issue does not allow the zone to be controlled. Check whether the error appears on all
thermostats; if it does, check that the main control board is operating properly. To resolve this
issue, make the following checks:
1.
Thermostat status: Check the thermostat's signal range from the main control board by
checking the Information parameter (see the section System advanced settings, System
parameters), or by bringing the thermostat closer to the main control board. If it re-
establishes communication, it will be necessary to relocate the thermostat because it was
not in signal range.
2.
Status of the main control board: Check that the power supply is correct.
3.
Status of the main control board: Check the correct functioning of the wireless
communication LEDs.
4.
Restart the zone and reassociate it to the system. To do this, press and hold on
and perform the initial system configuration process. Remember that, in order to associate
wireless devices, you should first open the wireless association channel, either through
the SW1 button on the main control board or from any thermostat in the Radio channel
parameter of the System advanced settings menu, Zone parameters.
5.
Restart the system: If you restart the system, this error may appear on the thermostats due
to the restart. This message should disappear in approximately 30 seconds once the restart
has been completed.
ERROR 1
ERROR 1
Steady
Switches
Error 5: Open circuit in temperature probe
Error 6: Short circuit in temperature probe
The zone loses the room temperature measurement, leaving the zone unable to generate
demand. In the event of such an incident, the device must be replaced or sent for repair.
The zone loses the room temperature measurement, leaving the zone unable to generate
demand. In the event of such an incident, the device must be replaced or sent for repair.