Window contact.
This option allows the control the state of a zone module based on the opening of the window. It
only has effect on the control element of the zone module. When this contact is on, if it detects any open window, it
turns off the zone after 60 seconds (displaying an Open window notification on the thermostat). It is off by default. In
order to activate this feature, configure it as Normally open or Normally closed.
•
Master address
(only available in installations configured as 4-pipe installations)
.
Sets the master zone, which imposes
its mode to this zone (only set-point temperature and fan speed features will be configurable). It is off by default.
•
Q-Adapt configuration.
Defines the individual weight of each zone to adapt the flow of the unit to the zone needs.
These are the features to be configured:
-
Automatic.
Default value. The system distributes proportionally its total weight (100) among the zone modules
in which the air stage is available.
-
Manual*.
It allows you to change the total weight of the zone. The weight displayed is the total of the main and
secondary zone modules. Range of values: 1-100 (accuracy: ±1).
*Note:
Total system weight may exceed 100.
The change of the fan speed depends on the configuration and typology of each zone of the installation. For further
information, please refer to the system's installation manual
•
Eco function.
(Only available in installations with fancoil zone module AZDI6ZMOFAN [C/R]).
Modify the setpoint
temperature (+/- 2.5 ˚C) for more efficient management of the thermal demand in its zone.
•
Steady ventilation.
(Only available in installations with fancoil zone module AZDI6ZMOFAN [C/R]).
This allows system
ventilation to be maintained even when no demand is being generated. This function is configured independently in
the heating and cooling modes.
•
DC fan voltage.
(Only available in installations with fancoil zone module AZDI6ZMOFAN [C/R]).
This system function
allows fan speeds to be adjusted according to the voltage specifications of the fancoil manufacturer.
•
Manufacturer ID
(only available in installations with AZDI6MCIFRC modules)
.
Select the control protocol you want to
use in the AC unit to be controlled.
Check the compatible IR gateway modules at:
(http://doc.airzone.es/producto/Gama_AZ6/Airzone/Distribuido/Fichas_tecnicas/Compatibilidades/UC_AZDI6MCIFR_MUL.pdf)
•
Reset thermostat
(not available in remote zones)
.
Allows you to reset the thermostat and returning it to the default
values.