Once configured, perform the connection with the radiant elements to control per each relay output of the module.
Control relay specs: Imax = 10 A at 110/230 V, voltage-free.
Note that to control elements with a greater power, it is recommended to use contactors in accordance
with the power required. Remember to connect the neutral connector directly from the circuit to the
element to be controlled.
Important:
The Airzone system is not compatible with electric duct heaters, it may result in system malfunction and/or fire.
4.- Connection to the ducted unit
-
Through gateway: Connect the communication gateway to the AC unit port of the main control board
. In order to
connect it to ducted unit,
follow the instructions of the communication gateway sheet
. It is recommended to install
the thermostat of the unit. For the connection of DIN rail gateways, use (2x0.22 mm
2
) Airzone wire. Use the shield only
on the connector of the main control board.
-
Through Start-Stop: Use the main control board relay
to perform the start-stop of the unit following the
manufacturer's instructions. I
max
1 A, V
max
24 / 48 Vdc.
5.- Connection of the zone modules with the elements/systems to control (Fancoil, Split, etc.)
You can find the instructions on how to connect these elements to the control modules on their data sheets.
6.- Connecting the thermostats
Connect each thermostat to the terminal corresponding to its zone module. Use (2x0.5+2x0.22 mm
2
) Airzone wire.
In case of Wireless element, check it has the battery on.
Terminals of zone module
Controller