background image

Refrigerant 

piping

Connection

 

 Page 29 

5. Clamp flare form on the end of the pipe. 

The end of the pipe must extend beyond 
the flare form. 

Flare form

Pipe

6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool 

clockwise until the pipe is fully flared. Flare 
the pipe in accordance with the dimensions 
shown in table .  

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, 
then connect it to the outdoor unit. You should 
first connect the low-pressure pipe, then the 
high-pressure pipe.  

1. When connecting the flare nuts, apply a 

thin coat of refrigeration oil to the flared 
ends of the pipes.  

2. Align the center of the two pipes that you 

will connect.  

Indoor unit tubing

Flare nut

Pipe

3. Tighten the flare nut as tightly as possible 

by hand. 

4. Using a spanner, grip the nut on the unit 

tubing.

5. While firmly gripping the nut, use a torque 

wrench to tighten the flare nut according 
to the torque values in table .  

NOTE: 

Use both a spanner and a torque 

wrench when connecting or disconnecting 
pipes to/from the unit.

• 

Ensure to wrap insulation around the piping. 
Direct contact with the bare piping may 
result in burns or frostbite.  

• 

Make sure the pipe is properly connected. 
Over tightening may damage the bell mouth 
and under tightening may lead to leakage.   

 CAUTION

8. Remove the flaring tool and flare form, 

then inspect the end of the pipe for cracks 
and even flaring.  

PIPING EXTENSION BEYOND FLARE FORM

  Pipe 
gauge 

Tightening 

torque

Flare dimension (A) 

(Unit: mm/ Inch)

Flare shape

M in.

M ax.

Ø 6.35

R0.4~0.8

45

°±

2

90

°      

±

4

A

Ø 9.52

Ø 12.7

Ø 16

Ø 19

Ø 22

65-67 N.m 

(663-683 kgf.cm)

23.2/0.91

23.7/0.93

75-85N.m 

(765-867 kgf.cm)

26.4/1.04

26.9/1.06

18-20 N.m 

(183-204 kgf.cm)

8.4/0.33

8.7/0.34

25-26 N.m 

(255-265 kgf.cm)

13.2/0.52

13.5/0.53

35-36 N.m 

(357-367 kgf.cm)

16.2/0.64

16.5/0.65

45-47 N.m 

(459-480 kgf.cm)

19.2/0.76

19.7/0.78

4. Remove PVC tape from ends of pipe when 

ready to perform flaring work.

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight 
seal.

1.  

After removing burrs from cut pipe, seal 
the ends with PVC tape to prevent foreign 
materials from entering the pipe. 

2.  

Sheath the pipe with insulating material.

3.

 

Place flare nuts on both ends of pipe. Make 
sure they are facing in the right direction, 
because you can’t put them on or change 
their direction after flaring. 

Flare nut

Copper pipe

Содержание SDMX R32

Страница 1: ...ly before installing or operating your new air conditioning unit Make sure to save this manual for future reference 21 AW SDMX 048 R32 UM IM EN FR SP POR 08 17 Rev01 English French Portugu s Espa ol F...

Страница 2: ...air conditioner SDMX R32 English Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference 21 AW...

Страница 3: ...of Contents Safety Precautions 04 Owner s Manual Unit Specifications and Features 08 1 Unit Parts 08 2 Operating temperature 08 3 features 09 Manual Operations 10 Care and Maintenance 13 Troubleshooti...

Страница 4: ...hole cover 8 Drill wall hole for connective piping 9 Connect drain hose Outdoor Unit Installation 1 Select installation location 2 Install drain joint 3 Anchor outdoor unit Refrigerant Piping Connecti...

Страница 5: ...urning smell immediately turn o the unit and disconnect the power Call your dealer for instructions to avoid electric shock re or injury Do not insert ngers rods or other objects into the air inlet or...

Страница 6: ...o power the unit Do not share the electrical outlet with other appliances Improper or insu cient power supply can cause re or electrical shock If connecting power to xed wiring an all pole disconnecti...

Страница 7: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 8: ...shall comply with ISO 14903 Amount of refrigerant to be charged kg maximum installation height m Minimum room area m 2 048 0 6m 35 2 048 3 0 0 6m 80 3 0 Model Btu h 30000 30000 48000 48000 0 6m 80 Eur...

Страница 9: ...e Room Temperature 17 C 32 C 62 F 90 F 0 C 30 C 32 F 86 F 10 C 32 C 50 F 90 F Outdoor Temperature 0 C 50 C 32 F 122 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical mo...

Страница 10: ...er press the manual button which will reset the horizontal louver settings Auto Restart some models In case of power failure the system will immediately stop To restart the unit press the ON OFF butto...

Страница 11: ...mode settings AUTO COOL DRY HEAT for cooling heating models only FAN ONLY Auto Automatically chooses the operation mode by sensing the di erence between the actual ambient room temperature and the set...

Страница 12: ...to be able to check view indoor outdoor fault code In other states press the and to adjust the temperature within a range of 16 C 17 C 30 C or 20 C 28 C To cut to 16 C 17 C or 20 C again when press d...

Страница 13: ...he remote controller seven times or more the Wireless module will enter into AP mode A long beep will be heard and the Wireless control indicator will ash quickly which means the user can do the next...

Страница 14: ...duce the cooling ef ciency of your unit and can also be bad for your health Make sure to clean the lter once every two weeks WARNING DO NOT REMOVE OR CLEAN THE FILTER BY YOURSELF Removing and cleaning...

Страница 15: ...lter do not touch metal parts in the unit The sharp metal edges can cut you Do not use water to clean the inside of the indoor unit This can destroy insulation and cause electrical shock Do not expose...

Страница 16: ...F or in COOL mode The noise is also heard when the drain pump optional is in operation A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s pl...

Страница 17: ...ription of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solution P...

Страница 18: ...xiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re seal if...

Страница 19: ...il The items are not included with the air conditioner must be purchased separately Name Shape Quantity PC Parts you must purchase separately Consult the dealer about the proper pipe size of the unit...

Страница 20: ...2 3 4 MC MC 6 Install the indoor unit INSTALLATION ORDER Install the outdoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Perform a test run Page 19 Installa...

Страница 21: ...ipe vent pipe Connection cable Connection pipe Refrigerant pipe port Air outlet Indoor unit Outdoor unit Outdoor unit A Outdoor unit B NOTE ON ILLUSTRATIONS Illustrations in this manual are for explan...

Страница 22: ...oise from the unit will not disturb other people Firm and solid the location will not vibrate Strong enough to support the weight of the unit A location at least one meter from all other electrical de...

Страница 23: ...oor unit has any fasteners holding it in place and tear o the notice sticker 2 Remove the fasteners from the roller according to the directions on the sticker 1 Measure the position of the holes for i...

Страница 24: ...place 3 Arrange the piping so that the drainage hose is on the bottom the connecting piping is in the middle and the electrical wiring is at the top Step 6 Piping and binding drainage electrical wiri...

Страница 25: ...DO NOTpull the drainpipe forcefully as this could cause it to disconnect Indoor Drainpipe Installation 1 Make sure the drain pipe is connected to the outdoor side downward 2 The hard polyvinyl chlorid...

Страница 26: ...rection of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind If the unit is frequently exposed to heavy rain or...

Страница 27: ...joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks in place facing the front of the unit 4 Conn...

Страница 28: ...ter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cause explosion and injury Refrigerant...

Страница 29: ...aintenance 1 Measure the distance between the indoor and outdoor units 2 Using a pipe cutter cut the pipe a little longer than the measured distance 3 Make sure that the pipe is cut at a perfect 90 an...

Страница 30: ...on around the piping Direct contact with the bare piping may result in burns or frostbite Make sure the pipe is properly connected Over tightening may damage the bell mouth and under tightening may le...

Страница 31: ...RE PERFORMING ANY ELECTRICAL WORK READ THESE REGULATIONS 1 All wiring must comply with local and national electrical codes regulations and must be installed by a licensed electrician 2 All electrical...

Страница 32: ...it 10 minutes or more before you touch the electrical components 10 11 12 WARNING BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK TURN OFF THE MAIN POWER TO THE SYSTEM Wiring NOTE ON AIR SWITCH When t...

Страница 33: ...5 9 of the wire b Strip the insulation from the ends of the wires c Using a wire crimper crimp the u lugs to the ends of the wires 2 Undo the screw on the cover of the electric control box and remove...

Страница 34: ...cuum for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn o the vacuum pump 7 Wait for 5 minutes then check tha...

Страница 35: ...dard pipe length is 5m 16 The refrigerant should be charged from the service port on the outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the followin...

Страница 36: ...stered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that...

Отзывы: