12-2
CONTROL SYSTEM
SM YBD018 1-A.1 GB
Definitions
Cool
Heat
MinFreq
MinFreqC
MinFreqH
MaxFreq
MaxFreqC
MaxFreqH
LoadDeadZone
LoadDeadZoneC LoadDeadZoneH
During running time (unlike starting) Compressor can operate only in its allowed
frequency range.
The lower allowed frequency is extracted from the following:
Mode
MinFreq MinFreqA
HP
HPA
Cool
MinFreqC MinFreqCA HPAtMinFreqC HPAtMinFreqCA
HP
Pressure
MinFreq
HPA
MinFreq
MinFreqA
Used only for ODU
NLOAD Calculation
Heat
MinFreqH MinFreqHA HPAtMinFreqH HPAtMinFreqHA
Notes:
1. HP stands for High Pressure.
2. Pressure is represented by the following:
x
Cooling:
max {OMT, OCT} in cooling mode,
x
Heating (Multi split):
maximum ICT among all active and available inactive IDUs in heating mode.
x
Heating (Single Split):
ICT
3.
The above parameters are determined from the compressor specifications.
The higher allowed frequency is extracted from the following:
Mode
‘Unit Night Mode’
Maximum Frequency (MaxFreq)
On
MaxFreqC
*0.75
Cool
Off
MaxFreqC
On
MaxFreqH
*0.75
Heat
Off
MaxFreqH