TR9230 VAV Zone Control For Temperature And CO

2

 

 Sequence Of Operation 

 

Setup 
 

The sensor shall have the following preset but adjustable parameters that can be 
adjusted through use of on-board keypad and display or via a PC interface.  These 
settings can also be preconfigured for the user by AirTest™ or a AirTest™ distributor.  

ï 

Space temperature set point for occupied mode is established. (factory setting is 
74ºF) 

ï 

Setback set point is set for unoccupied or setback mode (factory setting of 78ºF) 

ï 

User adjustable temperature band is set (factory set at +-2ºF)  

ï 

Select lowest allowable temperature (factory set at 3ºF below setpoint).  This will 
establish the point at which space ventilation will be limited to prevent over cooling of 
the space.  

ï 

Target cfm per person ventilation rate is set (factory set at 15 cfm/person) This will 
establish the upper limit of the proportional control band for ventilation.  

ï 

Select range 100% (0-10 V) or 50% (0-5V) range for the combined CO

2

 and 

ventilation output.  (Factory setting is 0-5 V) 

 

Operation 

 

1.  The controller shall measure both space CO

2

 and temperature, The controller will 

provide a modulation control signal to the VAV box actuator or fan based on the 
maximum value calculated for either temperature control using a PI control 
algorithm or CO

2

 using a proportional control algorithm designed to provide a 

predetermined target cfm/person to the space (e.g. 15 cfm/person).  
Temperatures for normal occupied mode shall be ___ºF .  And zone ventilation 
shall be controlled to ___ cfm/person.  

 
2.  If the demand for ventilation causes the temperature to drop below set point, the 

controller shall provide a binary closed contact signal intended to activate a 
heating coil in the VAV box to prevent over cooling of the space and to maintain 
set point.  

 

3.  The controller shall also be designed to override the demand for ventilation if the 

space temperature drops ___ ºF below the temperature setpoint.  

 
4.  Manual push buttons on the wall mount controller shall allow users to control the 

deviation of the temperature setpoint adjustment to a limit of +/- ___ degrees 
from the set point programmed into the controller. This adjusted setpoint will be 
maintained until the system reverts to a setback mode.  Upon returning from 
setback the sensor shall control temperature based on the original programmed 
setpoint until the buttons are adjusted again.  

 

5.  If indoor CO

2

 concentrations drop to a level where it is clear there is no 

occupancy in the space (within 50 ppm of baseline concentrations).  The system 