En-6
Perform wiring so that water does not enter this unit
along the external wiring. Always install a trap to the
wiring or take other countermeasures. Otherwise it will
cause trouble, electric shock, or fire.
Confirm the name of each unit and name of each
terminal block of the unit and connect the wiring in
accordance with the directions given in the manual so
that there is no incorrect wiring. Incorrect wiring will
damage the electric parts and cause smoke and fire.
When installing the connection cables near a source
of electromagnetic waves, use shielded cable. Other-
wise, a breakdown or malfunction could result.
When wiring between the outdoor unit, indoor unit,
▪
and touch panel controller, refer to the indoor unit and
outdoor unit installation manuals.
Always connect both ends of the
▪
earth (ground) con-
nection of the transmission cable.
Install the disconnect switch to the easily accessible
▪
location.
Install the fuse (5A) to the L line of power supply cable.
▪
L N
X1 X2 Y1Y2Y3
L N
X1 X2 Y1Y2Y3
L N
X1 X2 Y1Y2Y3
L N
X1 X2 Y1Y2Y3
L N
X1 X2 Y1Y2Y3
L N
X1 X2 Y1Y2Y3
1Ø 50/60Hz
100-240V
L N
X1 X2
1Ø 50/60Hz
100-240V
L N
X1 X2
X1 X2
Z1 Z2
H1 H2
Outdoor unit
(Master)
Touch panel
controller
Indoor unit
Power
supply
Power
supply
Power
supply
Power
supply
Power
supply
Power
supply
Power
supply
Transmission
Power
Supply
Transmission
Wired remote
controller
Wired remote
controller
Touch panel
controller
Fuse (5A)
Switch
(Disconnect switch)
2 remote
controllers
Wireless
remote
controller
Fuse (5A)
Switch
(Disconnect
switch)
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
2 remote
controllers
Trans-
mission
Trans-
mission
Trans-
mission
Trans-
mission
Trans-
mission
Trans-
mission
Trans-
mission
Trans-
mission
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Power
Supply
Power
Supply
Power
Supply
Power
Supply
Power
Supply
Power
Supply
Power
Supply
Wire the transmission cable to any one of the following:
▪
Transmission terminal block inside the indoor unit
(Fig. 1)
External terminal block (Field supplied)
(Fig. 2)
Transmission terminal block inside the outdoor unit
(Fig. 3)
1
Fig1
Touch panel
controller
Refrigerant
system 1
Refrigerant
system 2
2
Fig1
External terminal block
Touch panel
controller
Refrigerant
system 1
Refrigerant
system 2
3
Fig1
Touch panel
controller
Refrigerant
system 1
Refrigerant
system 2
Installation method
51 51
Install the switch box in advance to the wall to which
▪
the touch panel controller is to be installed.
Installation procedure
(1)
Verify that the
power supply cable and transmission
cable are wired to the switch box.
Peel the cable covering.
Decide the path the
power supply cable and transmis-
sion cable are to follow up to the terminals of the touch
panel controller.
After passing the
power supply cable and transmis-
sion cable through the specified holes of the instal
-
lation plate, fix the installation plate to the switch box
using screws.
Adjust the tilt of the installation plate by installing the
accessory washers.
In addition, pass the
power supply cable and trans-
mission cable through the wiring hole of the rear
cover and fix the rear cover using the tapping screws
(M4 x 8mm, 2 screws) supplied with the installation
plate.
Next, fix the rear cover to the wall using the 2 acces
-
sory screws (M4 x 20mm) and accessory washers.
Fix the cables at 2 places by binders.
7
Provide a surplus of 5mm or more from the end of the
covering of the cable and fix the part which is fixed by
the binders.
Fix the
power supply cable and transmission cable to
their respective terminal so that there is no mistake.
Tightening torque
Power supply
cable
1.2 to 1.8 N
•
m
(10.7 to 15.9 lbf
•
in)
Transmission
cable
0.8 to 1.2 N
•
m
(7.1 to 10.6 lbf
•
in)