AirSpeed 1050 Installation Guide
DUG01545
Airspan Commercial and Internal Use
26
Tip:
It is good practice to label both ends of the cable to identify which AirSpeed 1050 unit it is
connected to.
Tip:
It is good practice to leave a spare loop of cable (approximately 0.5m). This will allow for
easier wiring and will allow the cable to be re-terminated if necessary in the future.
Note:
When securing the cable make sure there is no tension on the cable so that it is easy to
disconnect and re-connect for future maintenance actions.
5.2.1 AC Cable Preparation
Caution:
Safety - Disconnection of power supply
When AirSpeed unit is connected directly to wiring a suitably rated and easily accessible
circuit breaker shall be incorporated externally to the equipment.
Power source disconnection is required before disconnecting the power connector.
Warning:
This unit incorporates
double pole
/
neutral fusing
. Both the Line & Neutral have fuses
in them.
Warning:
The onsite source circuit breaker (6A) should be gang operated,
two
(
2
)
pole
(single
phase type).
Note:
Required AC power cable – 3 wire - 18 AWG within a pipe enclosure, connected directly to
the building electrical power supply.
The following displays the proper steps for AC cable preparation:
1. Strip back and remove the outer sheath to expose the inner insulated wires to a length of
34mm max (1.34 in). Then strip back 8mm± 2 (0.31 in) of the inner core insulation.
Figure 12: Stripping Dimensions (AC Cable)
2. Open the housing lock by sliding up then lift the clamp handle.
Figure 13: Open Housing Lock