The controls
are to be surface mounted onto a wall. Only one master
control should be installed to a ventilation system (the face plate on
this illustration may not be exactly the same as yours).
1.
Separate the face plate from the back plate by firmly
pulling apart (Figure A). Be careful not to damage face
plate contact pins.
2.
For mounting the control without a Decora plate, break off
top and bottom tabs and refer to Figure C for mounting.
3.
Place the back plate of the control in the desired location
on the wall and pencil mark the top and bottom screw
holes (Figure B
or C
).
4.
Remove the back plate and mark the center hole for the
wires in the middle of the screw holes. Refer to Figure B
or
C for
placement
.
5.
Cut in a 3/4 in by 1 in oval hole in the wall to allow for the
wire opening and drill (two) 1/8 in holes for the screws
and
wall anchors (Figure B
or C
).
6.
Pull 3 wire 20 gauge (min.) 100 ft length (max.), through
the opening in the wall
.
7.
Connect red, green, and yellow to the wiring terminals
located on the back plate (Figure B
or C
).
8.
Attach the back plate to the wall using the 2 supplied
screws and anchors.
9.
Attach the face plate to the back plate (Figure A). Note:
Be
careful to correctly align the face plate to avoid
damaging
the face plate contact pins.
10.
Connect the 3 wire 20 gauge (min.) 100 ft length (max.)
to
the terminal block located on ventilator (Figure
D
).
ATTENTION
Control Installation
and Operation
Instructions
Pay special attention not to damage
the contact pins when removing and
at
taching the face plate (Figure
A
).
TI-BC02
0
7_10
_15
Turning on the Control
Press and release the ON/OFF button . The light above will
illuminate.
Setting the Ventilation Speed
Press and release the Fan button to select
LOW
or H
IGH
fan speed. The corresponding “Indicator Light" will illuminate. If both
LO and HI indicator lights are off, the fan is OFF but will turn ON if required by the Dehumidistat or remote Timer (if installed).
Humidity Control
Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels. This feature is only
effective when the outdoor temperature is below 59˚F (15˚C).
Setting the Dehumidistat
Press and release the Dehumidistat button until the Dehumidistat L
ight
is at the desired setting. After a few seconds the
Dehumidistat light will either flash or be on continuous.
A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation. A
continuous light indicates the humidity level is lower than the setting. Refer to the unit's Home Owner’s manual for instructions on
how the Dehumidistat works.
The Dehumidistat will override the current speed setting to
HIGH
speed.
The Dehumidistat function can be turned OFF by pressing the button until no Dehumidistat light is on.
Note
- Only 1 Dehumidistat should be installed in a system.
Figure A
Red #3
Yellow #4
Green #5
Figure D
Keep top / bottom
vent openings clear
Figure B
1.625"
0.75
"
1
"
1.625"
1/8 in hole for
screw and
anchor
1 in x 3/4 in
for wire
opening
Wiring
Terminals
1/8 in hole
for screw and
anchor
oval hole
Break off tab
Alternate Wall Mount
1/8 in hole for
screw and
anchor
1 in x 3/4 in
0.75
"
oval hole
1/8 in
for wire
hole for
opening
screw and
anchor
Wiring
Terminals
Break off tab
Figure C
1
"
Wire hole
centered
between
screw
holes
Back Plate
Face Plate