background image

1      

2      

3      

4      

5     

6     

7     

8      

9     

10

11    

12    

13    

14    

15    

16    

17   

18    

19   

20   

21

SEE

POWER

CONNECTIONS

REMOTE

 ACCESSORIES

ALARM

CONTACTS

12 A

ALARM

CONTACTS

12 A

*TROUBLE

CONTACTS

10-A

*TROUBLE CONTACTS ARE SHOWN

 IN NON-ENERGIZED CONDITION.

UNDER NORMAL OPERATION

CONTACTS WILL BE REVERSED.

FIREX DUCT SMOKE DETECTOR

SM-501 DUCT SMOKE DETECTOR

SEE

POWER

CONNECTIONS

ALARM

CONTACTS

10A

ALARM

CONTACTS

10A

*TROUBLE

CONTACTS

10A

REMOTE

ACCESSORIES

*TROUBLE CONTACTS ARE SHOWN
IN NON-ENERGIZED CONDITION.
UNDER NORMAL OPERATION CON-
TACTS WILL BE REVERSED.

INST APD0191 C081230

WIRING

*

CAUTION

:  For terminals 7-15 do not use looped wire under terminals.  Break wire run to provide for proper supervision of connections.

With detector head removed, connect one of the appropriate dedicated power sources to the applicable terminals (see above).  Replace detec-
tor head and the unit will be energized.  The green pilot LED will be illuminated, and when pressing the test/reset button, the red alarm LED
will be illuminated.  This test confirms the correct basic operation of the duct smoke unit, excluding the detector head (see functional testing).  

In the event of a fire alarm, certain equipment may be required to be shut down.  For example, shut down may be achieved by interrupting the
fan supply source to that particular piece of equipment when wired as indicated below.

EXAMPLE: 

FAN SUPPLY SOURCE

7

9

NC         

C             NO

ALARM RELAY

5

6

1

DEDICATED INPUT VOLTAGE

115VAC

8

ELECTRICAL INSTALLATION

POWER CONNECTIONS

Prior to connecting input power to the duct unit, determine the correct input voltage/ current availability and ensure it is connected to the
correct terminals.

In alarm 7 and 8 will
open, interrupting
voltage supply to fan

3

AC/+ /H

AC/- /N

2

3

or

24VAC/VDC

24VAC/VDC INPUTS

Terminals 5, 6

24VAC

50/60  Hz     0.2A  MAX.

24VDC

0.1A  MAX.

115VAC   50/60 Hz

0.1A  MAX.

115VAC INPUT

Terminals 1,2,3.

230VAC   50/60 Hz

0.1A  MAX.

230VAC INPUT

Terminals 1,2,4.

24VDC OPERATION

115VAC OPERATION

230VAC OPERATION

+     -

G       H1              H2

24VAC OPERATION

Отзывы: