Air Products & Controls SL-701 Скачать руководство пользователя страница 1

 

 

Tech Support # 1-888-332-2241

                                 

      

                                                     

INST SL-701 110124 

or 1-248-332-3900 

To get FPM from 

CFM

CFM / (

Duct

 W’ x Duct H’) 

SL-701 DUCT CARBON MONOXIDE DETECTOR KIT 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 
 

PRODUCT OVERVIEW 

 

CONTENTS 

 

SL-701 Duct Carbon Monoxide Detector

 

 

MSR-50/CO Remote Accessory

 

 

FAST Sample Tube Assembly Kit

 

 

8” FAST Exhaust Tube

 

 

Mounting Template and Screws

 

 
 

SL-701 SPECIFICATIONS 

 

Input Power  Standby 

Current 

Alarm 
Current 

24VAC 

43 mA 

246 mA 

24VDC 

28 mA 

187 mA 

115VAC 

23 mA 

50 mA 

230VAC 

11 mA 

28 mA 

 

Relay Contact Ratings: 

Alarm contacts: (2) Sets of form “C” rated 10A @ 
115VAC resistive (1) form “A” rated at 2A 
Trouble contacts: (1) Set of form “C” rated 10A @ 
115VAC resistive 

 

Air Velocity: 

100 to 4000 feet per minute 

 

Ambient temperature: 

32˚F to 140˚F (0˚C to 60˚C) 

 

Humidity: 

10% to 85% RH Non-Condensing/Non-Freezing 

 

Dimensions:

  

13 ½”L × 4 ½“W × 2 ¼“D 

 

MSR-50/CO SPECIFICATIONS 

Current Draw 

Standby 0 mA 

Alarm 105 mA 

Audible 

Hi 69 db @ 10’  Lo 54 db @ 10’ 

Format 

ANSI Temporal 

Continuous 

Visual 

2 CD on axis 

1 HZ (1/S) 

PRODUCT APPLICATION 

The  SL-701  duct  carbon  monoxide  detector  kit 
provides early detection of carbon monoxide in

 

air 

moving  through  the  HVAC  duct  supply,  return,  or 
both  in  commercial,  industrial,  or  residential 
applications.  Complete  HVAC  systems  can  be  shut 
down  in  the  event  of  carbon  monoxide  detection. 
The  included  MSR-50CO  remote  accessory  can  be 
used  to  provide  Private  Mode  (non-public)  audible 
and  visual  alarm  indication  in  a  remote  location. 
Combination CO / Fire alarm control units can, and 
must,  be  notified  of  an  alarm  or  trouble  condition 
to  provide  Public  Mode  Notification  and  Remote 
Reporting. 

 
NOTE: The SL-701 is intended to be connected to 
a  fire  alarm  control  unit  or  combination  control 
unit if present. Please refer to NFPA 720 (Standard 
for  the  Installation  of  Carbon  Monoxide  (CO) 
Detection  and  Warning  Equipment)  and  NFPA  72 
(National Fire Alarm and Signaling Code). 

 

This  is  not  a  duct  smoke  detector  (UL  268A)  or 
“CO  alarm”  (UL  2034)  and  is  not  designed  to 
detect  smoke,  fire  or  any  gas  other  than  carbon 
monoxide  as  caused  by  fossil  fuel  fired  appliances 
and / or as introduced from the outside in fresh air 
intakes  in  the  HVAC  system.  The  SL-701  is  a  CO 
system detector (UL 2075). 

 

PRODUCT DESCRIPTION 

The  SL-701  duct  mounted  carbon  monoxide 
detector  is  fitted  with  an  electrochemical  sensor 
that  is  able  to  detect  four  levels  of  carbon 
monoxide  and  has  a  life  of  approximately  six  years 
in normal environmental conditions. 
NOTE:  Areas  of  high  or  low  temperature  and  low 
humidity  will  reduce  the  life  expectancy  of  the 
sensor. In all cases, an end of life trouble report will 
be signaled. 
The  detector  has  two  sets  of  form  “C”  alarm 
contacts,  one  set  of  form  “A”  alarm  contacts,  and 
one  set  of  form  “C”  trouble  contacts.  The  alarm 

 

Содержание SL-701

Страница 1: ...event of carbon monoxide detection The included MSR 50CO remote accessory can be used to provide Private Mode non public audible and visual alarm indication in a remote location Combination CO Fire a...

Страница 2: ...gas that results from the incomplete combustion of fossil fuels It is often referred to as the silent killer because it is virtually impossible to detect without sensing technology Through the normal...

Страница 3: ...d with the kit must be installed at the end of the sampling tube NO TOOLS TUBE INSTALLATION The SL 701 Series duct carbon monoxide detector provides a unique patented mechanism for installation and or...

Страница 4: ...ormally open The other set of 10 amp alarm contacts are terminals 7 and 18 being normally closed and 8 and 18 being normally open Rated at 10A 115VAC resistive Wiring examples are shown below Your wir...

Страница 5: ...e remote accessory at the pin connector marked STROBE Secure the modules in a standard 4X4 electrical box with the provided screws and install the provided cover plate The SL 701 provides a 2 amp form...

Страница 6: ...lid and the yellow fault LED on the sensor will stay off The green LED on the circuit board and remote will continue to stay on If there are problems during the warm up the LED s will continue to alte...

Страница 7: ...on after the test has ended Carbon monoxide spray test for the sensor In order to use the TG 701 CO test gas sold separately the detector must be put into user test mode Press and hold the test reset...

Страница 8: ...On Red On Green Red On Pushing test reset on detector or turning the key on remote Green 0 5 second flash Off Off On Green Green Off User test mode is in progress Red Solid On Off On Red On Green Red...